Huawei UA5000 Manual

Environment monitoring
Hide thumbs Also See for UA5000:
Table of Contents

Advertisement

UA5000 Universal Access Unit
V100R019C06
Environment Monitoring
Issue
01
Date
2012-08-17
HUAWEI TECHNOLOGIES CO., LTD.

Advertisement

Table of Contents
loading

Summary of Contents for Huawei UA5000

  • Page 1 UA5000 Universal Access Unit V100R019C06 Environment Monitoring Issue Date 2012-08-17 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 All other trademarks and trade names mentioned in this document are the property of their respective holders. Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope.
  • Page 3 Indicates a tip that may help you solve a problem or save your time. Provides additional information to emphasize or supplement important points of the main text. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 4 Based on issue 02 (2011-03-25) of V100R019C01, V100R019C06 has the following changes: The following information is added: 8 ETP4890 Monitoring Solution The following information is modified: 2 Environment Monitoring Application 6.3 Checking Environment Monitoring Cables Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 5: Table Of Contents

    7.2 PMIB01 Sensor Transfer Box..........................89 7.3 PMIB02 Sensor Transfer Box..........................93 7.4 Checking Environment Monitoring Cables......................96 7.5 Configuring the Environment Monitoring Parameters of the EPS75-4815AF..........107 8 ETP4890 Monitoring Solution....................121 Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 6: Table Of Contents

    10.2.5 Installing the Smoke Sensor........................196 10.2.6 Installing the Water Sensor........................199 10.2.7 Installing the MDF Sensor........................201 10.2.8 Installing the Surge Protector Sensor....................202 10.2.9 Installing the Battery Temperature Sensor..................203 Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 7: Environment Monitoring Principles

    The monitoring module of the power system then processes the environment information and reports the information to the control system. With the sensor transfer box, the monitoring function is extended. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 8: Basic Concept

    Generally, the built-in analog parameter is fixed. Except the upper and lower alarm thresholds, users cannot modify other built-in analog parameters. The extended analog parameters can be modified, and users can configure the analog sensors as required. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 9: Environment Monitoring Principle (Esc)

    The ESC processes the collected monitoring parameters and then reports the parameters to the control system. l The network management center (EMS center) can monitor alarms remotely. l Dry contact signals refer to passive digital signals. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 10: Environment Monitoring Principle (Power System+Sensor Transfer Box)

    The EMU reports the monitored parameters collected by the sensor transfer box to the control system. l The network management center (EMS center) can monitor alarms remotely. l Dry contact signals refer to passive digital signals. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 11: Environment Monitoring Application

    One HABD shelf F01D500 One HABD shelf+one HABF shelf F01D1000 Two HABD shelves+one HABF shelf EPS75-4815AF+PMIB02 F02AF (AC-powered) One HABD shelf+one HABF shelf EPS30-4815AF+PMIB01 M200 (AC-powered) One HABM shelf Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 12: H303Esc Monitoring Solution

    3.3 Configuring the Environment Monitoring Parameters of the H303ESC Board This topic describes how to configure the environment monitoring parameters of the H303ESC board through the CLI. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 13: H303Esc Emu

    Status Description On for 1s and off for 1s The EMU works in the normal repeatedly state 0.5s on and 0.5s off repeatedly The EMU is faulty Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 14 JAB1 Socket for the buzzer Connected to the buzzer on the cabinet JTP1 Socket for the MDF sensor Connected to the alarm unit on the MDF Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 15 The H303ESC board resides in the right of the EMU and provides two DIP switches: S6 and S7, and six jumpers: S1, S2, S3, S8, S10, and S11, as shown in Figure 3-3. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 16 The H303ESC board is used in the exchange S7-2 The H303ESC board uses one serial port for reporting The H303ESC board uses two serial ports for reporting S7-3 Reserved Unavailable Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 17 Table 3-7. Table 3-7 Settings of H303ESC S11 Jumper Setting Meaning Default Setting Pins 1-2 The running status LED is valid Pins 1-2 connected connected Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 18: Checking Environment Monitoring Cables

    TEST HWTB N-485 N-485 N-ESC N-ESC PWR-ALM FAN-ALM TEST View of fan backplane (up) HABA N-485 N-485 N-ESC N-ESC PWR-ALM FAN-ALM TEST View of fan backplane (down) Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 19 By referring to the connection diagram, check whether the connections from each sensor to the H303ESC board and from the H303ESC board to the control system are correct. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 20 The Other End Connects to... Position Position Monitoring cable of MONITOR PORT of H303ESC JTD1 the J2-type PDU J2-type PDU H303ESC JTD2 H303ESC JTD3 H303ESC JTD4 H303ESC JTD5 Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 21: Configuring The Environment Monitoring Parameters Of The H303Esc Board

    Displayed on the Host Analog 0 Temperature Temperature Analog 1 Humidity Humidity Analog 2 JTA1 Not connected by default, used to add a user-defined monitoring analog parameter Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 22 Not connected by default, used to add a user-defined monitoring digital parameter Digital 13 JTD12 Not connected by default, used to add a user-defined monitoring digital parameter Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 23 Upper alarm threshold of When the ambient temperature of the device analog parameter 0: 50 is equal to or higher than 50°C, the host reports an alarm. Default: 55°C. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 24 Valid level of digital When the high level represents the valid parameter 0: high level level, the host does not report an alarm in the case of high level. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 25 Valid level of digital When the low level represents the valid level, parameter 5: low level the host does not report an alarm in the case of low level. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 26 Add an EMU emu add Query the EMU status display emu Query the system display esc system parameter configuration Query the environment display esc environment info information Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 27 The following considers the configuration in the F02A cabinet as an example to describe the process of configuring the environment monitoring parameters of the H303ESC board. Log in to the UA5000 through the maintenance terminal and add an EMU. huawei(config)#emu add 0 H303ESC 0 30 rs232 H303ESC Query the status of the H303ESC board.
  • Page 28 The results show that certain monitoring parameters, such as temperature, humidity, door status, and MDF, have been configured automatically in the system. Other monitoring parameters, however, need to be configured manually. Configure the analog parameters. huawei(config-if-h303esc-0)#esc analog 0 alarm-upper-limit 50 alarm-lower- limit 10 huawei(config-if-h303esc-0)#esc analog 1 alarm-upper-limit 80 alarm-lower- limit 5...
  • Page 29 Close all the doors of the cabinet, and confirm that the buzzing tone disappears. Query the environment information again, and confirm that no door status alarm is generated. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 30: H304Esc Monitoring Solution

    4.3 Configuring the Environment Monitoring Parameters of the H304ESC Board This topic describes how to configure the environment monitoring parameters of the H304ESC board through the CLI. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 31: H304Esc Emu

    Name Status Description Buzzer switch The communication between the monitoring unit and the host is normal The communication between the monitoring unit and the host is faulty Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 32 4-20 mA current or the 0-5 V voltage l Selecting the type of the accessed signals through the DIP switches JTA4-JTA6 Not available Not available Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 33 The H304ESC provides two DIP switches: S2 and S3, and five jumpers: S4-S8, as shown in Figure 4-2. Figure 4-2 Layout of the H304ESC DIP switches H304ESC 12 3 Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 34 Unavailable S3-4 The reporting rate of the serial port is 19200 bit/s The reporting rate of the serial port is 9600 bit/ S3-5 to S3-8 Reserved Unavailable Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 35 By referring to the cable connection diagram, check whether the connections from each sensor to the H304ESC board and from the H304ESC board to the control system are correct. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 36 Monitoring cable of MONITOR PORT of JTD1 port of the H304ESC the C-type PDU the C-type PDU JTD2 port of the H304ESC JTD3 port of the H304ESC Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 37 By referring to the cable connection diagram, check whether the connections from each sensor to the H304ESC board and from the H304ESC board to the control system are correct. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 38 Monitoring cable of MONITOR PORT of JTD2 port of the H304ESC the H-type PDU the H-type PDU JTD3 port of the H304ESC JTD4 port of the H304ESC Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 39 JTD1 port of the H304ESC subtending cable the HWTF transfer board of the HABF (D) shelf Door status sensor Door status sensor JTM1 terminal of the connecting cable H304ESC Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 40: Configuring The Environment Monitoring Parameters Of The H304Esc Board

    Digital 1 JTM1 (door Door status sensor Door status sensor status) Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 41 HABD shelf parameter. Digital 14 Reserved Unavailable Unavailable Digital 15 Reserved Unavailable Unavailable Digital 16 Reserved Unavailable Unavailable Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 42 Analog parameter ID: 0 This analog parameter is set according to the parameters actual requirements. The built-in analog parameter is set here to monitor the ambient temperature of the device. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 43 MDF sensor is set here to monitor the MDF status. When the MDF is faulty, the host reports an alarm. Allocated by default (unable to be changed by the user). Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 44 Valid level of digital When the low level represents the valid level, parameter 5: low level the host does not report an alarm in the case of low level. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 45 Valid level of digital When the low level represents the valid level, parameter 11: low level the host does not report an alarm in the case of low level. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 46 IDs in the system (1: temperature; 2: humidity; 3: voltage; 4: current), and IDs 5-20 are alarm IDs allocated to other user-defined alarms by users. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 47 H304ESC board. Log in to the UA5000 through the maintenance terminal and add an EMU. huawei(config)#emu add 0 H304ESC 0 30 rs232 H304ESC Query the status of the H304ESC board.
  • Page 48 5 alarm-upper-limit 80 alarm-lower- limit 0 name Humidity sensor-type 0:voltage analog-alarm 2 unit %RH Configure the digital parameters. huawei(config-if-h304esc-0)#esc digital 2 available-level low-level name SPD1 huawei(config-if-h304esc-0)#esc digital 3 available-level low-level name SPD2 huawei(config-if-h304esc-0)#esc digital 4 available-level low-level name SW1...
  • Page 49 Close all the doors of the cabinet, and confirm that the buzzing tone disappears. Query the environment information again, and confirm that no door status alarm is generated. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 50: Escm Monitoring Solution

    5.3 Configuring the Environment Monitoring Parameters of the ESCM This topic describes how to configure the temperature, door status, MDF and power supply monitoring parameters of the ESCM. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 51: Escm Emu

    (for unfastening) Captive screw Holes for the M3 sunk Plastic foot screw (for fastening) Front Panel Figure 5-2 shows the front panel of the ESCM EMU. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 52 Alarm of the external digital parameter Blinks irregularly An application program is being loaded or upgraded online. The loading speed determines the frequency of blinking. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 53 Communicates with the upper system in the RS-232 Supported or RS-485 mode. l Supports the RJ45 connector. l Connects to the communication port of the standby control board. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 54 Terminal block for environment Power socket parameter S1 has eight available electrical switches. ON indicates 0, and OFF indicates 1. Table 5-3 describes the settings of SW1. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 55 Table 5-4 shows the settings of SW1-1 to SW1-4. Table 5-4 Settings of SW1-1 to SW1-4 SW1-4 SW1-3 SW1-2 SW1-1 Address Value Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 56 By referring to the cable connection diagram, check whether the connections from the sensors to the ESCM and from the ESCM to the control system are correct. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 57: Configuring The Environment Monitoring Parameters Of The Escm

    5.3 Configuring the Environment Monitoring Parameters of the ESCM This topic describes how to configure the temperature, door status, MDF and power supply monitoring parameters of the ESCM. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 58 Before adding a user-defined analog or monitoring digital parameter, make sure that the port corresponding to this analog or monitoring digital parameter is properly connected with an environment monitoring cable. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 59 Lower alarm threshold of When the humidity of the device is equal to analog parameter 2: 0 or lower than 0% RH, the host reports an alarm. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 60 The monitoring parameters can be reported to the control board only when the data of the ESCM is correctly configured in the system. Figure 5-5 shows the configuration process, and Table lists the commands used during the configuration. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 61 1-4 are reserved alarm IDs in the system (1: temperature; 2: humidity; 3: voltage; 4: current), and IDs 5-20 are alarm IDs allocated to other user-defined alarms by users. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 62 The following considers the configuration in the M200 cabinet as an example to describe the process of configuring the environment monitoring parameters of the ESCM. Log in to the UA5000 through the maintenance terminal and add an EMU. huawei(config)#emu add 0 MiniESC 0 30 rs232 MiniESC Enter the ESCM configuration mode and query the default analog and digital parameters.
  • Page 63 2 alarm-upper-limit 80 alarm-lower- limit 0 name Humidity sensor-type 0:voltage analog-alarm 2 unit %RH Configure the digital parameters. huawei(config-if-MiniESC-0)#esc digital 9 available-level low-level name szl9 digital-alarm Query the default configuration of the analog and digital parameters. huawei(config-if-MiniESC-0)#display esc environment info...
  • Page 64: Eps30-4815Af Monitoring Solution

    EPMU03 to the control system are correct. 6.4 Configuring the Environment Monitoring Parameters of the EPS30-4815AF This topic describes how to configure the environment monitoring parameters of the EPS30-4815AF through the CLI. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 65: Eps30-4815Af Power System

    EPS30-4815AF power system. Table 6-1 Component configuration of the EPS30-4815AF power system Component Configuration GERM4815T rectifier module 1 to 2 (optional) EPMU03 monitoring module Rack-EPS30-4815AFEM AC/DC power supply unit Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 66 The rectifier module functions properly. Table 6-4 describes the indicators on the monitoring module of the EPS30-4815AF power system. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 67 Figure 6-3 shows the output terminals of the EPS30-4815AF power system. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 68 Table 6-5 Mapping between the fuses of the output tributaries and the load tributaries Fuse of the Output Tributary Load Tributary FU-1 (10 A) LOAD1 (10 A) FU-2 (20 A) LOAD2 (20 A) Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 69 The DIP switchs 1-5 are used to set the address of the environment monitoring module, Table shows the settings of the Dip switchs. Table 6-7 Settings of the Dip switchs 1-5 Address Value Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 70 ≥ 89% (in rated working state, 50% to 100% load) Operating temperature range -33°C to +65°C (Note that in the range of +50°C to +65°C, the output current also decreases linearly, limited within a specified range.) Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 71: Pmib01 Sensor Transfer Box

    PMIB01 sensor transfer box. Figure 6-5 Front panel of the PMIB01 sensor transfer box Sensor Port Figure 6-6 Table 6-9 describe the sensor ports of the PMIB01 sensor transfer box. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 72 Pin 1 and pin 3 are for the +24 V power supply. temperature and l Pin 2 is for the temperature signal cable. humidity 1 l Pin 4 is for the humidity signal cable. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 73 Pin 1 is for the signal cable FU1+ and is connected battery fuse to the negative pole of the battery. l Pin 2 is reserved for the FU1- signal. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 74 By referring to the cable connection diagram, check whether the connections from the sensors to the PMIB01, from the PMIB01 to the EPMU03, and from the EPMU03 to the control system are correct. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 75 Connect One End of the Connect the Other End Cable to... of the Cable to... MDF monitoring cable JTP1 terminal of the sensor Alarm bar of the MDF transfer box Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 76: Configuring The Environment Monitoring Parameters Of The Eps30-4815Af

    Not connected by default, used to add a user-defined monitoring digital parameter Digital 4 JTD5 Not connected by default, used to add a user-defined monitoring digital parameter Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 77 The subnode ID must be the same as the subnode setting of the corresponding DIP switch on the EMU, but the subnode ID must be different from IDs of the other subnodes on the same bus. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 78 If the continuous float charging days duration of the rectifier unit exceeds the preset equalized charging interval, the battery enters the equalized charging state. Default: 60 days. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 79 This parameter is set according to the actual 44 V requirements. Default: 43.5 V. Battery set power-off This parameter is set according to the actual voltage: 43 V requirements. Default: 43 V. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 80 This parameter is set according to the actual discharging start time: 0 requirements. Default: 0h. Battery auto- This parameter is set according to the actual discharging duration: 2 h requirements. Default: 2h. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 81 10% requirements. When the actual humidity is equal to or lower than the lower alarm threshold, the system reports an alarm. Default: 10% RH. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 82 EPS30-4815AF is configured correctly in the system. Figure 6-8 shows the configuration process, and Table 6-14 lists the commands used during the configuration. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 83 Configure the power supply power off load power-off and battery set power-off parameters Configure the power power supply-parameter distribution parameters Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 84 The following considers the configuration in the F01E400 cabinet as an example to describe the process of configuring the environment monitoring parameters of the EPS30-4815AF. Log in to the UA5000 through the maintenance terminal and add an EMU. huawei(config)#emu add 0 POWER4845 0 0 RS232 POWER4830 Query the status of the EPS30-4815AF.
  • Page 85 If the planned data is the same as the query result, the parameters need not be configured. If the parameters need to be modified, run the power charge command. Configure the battery management parameters. huawei(config-if-power4845-0)#power battery parameter 0.15 60 1 75 Configure the temperature compensation coefficient of the battery. huawei(config-if-power4845-0)#power battery temperature 80 -20 80 Configure the power supply load power-off and battery set power-off parameters.
  • Page 86 1 loop : connect environment Temperature : Normal environment Humidity : Normal door alarm : Alarm water alarm : Normal fog alarm : Normal module 0 : normal Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 87 15. Save the data. huawei(config-if-power4845-0)#quit huawei(config)#save 16. Close all doors of the cabinet. Then, query the alarm information again, and confirm that there is no alarm for any monitoring parameter. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 88: Eps75-4815Af Monitoring Solution

    EPMU02T, and from the EPMU02T to the control system are correct. 7.5 Configuring the Environment Monitoring Parameters of the EPS75-4815AF This topic describes how to configure the environment monitoring parameters of the EPS75-4815AF through the CLI. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 89: Eps75-4815Af Power System

    EPS75-4815AF power system. Table 7-1 Component configuration of the EPS75-4815AF power system Component Name Configuration GERM4815T rectifier module 2 to 5 (optional) Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 90 The yellow LED blinks. The communication of the rectifier module is interrupted. The yellow LED is off. The rectifier module works in the normal state. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 91 Figure 7-2 Input terminals of the EPS75-4815AF power system AC input BATT. LOAD1 LOAD2 LOAD3 LOAD4 1- 2- AC-L AC-N B1 B2 1- 2- LOAD(-) BATT.(+) LOAD(+) BATT.(-) Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 92 Figure 7-4 Output tributary switches of the EPS75-4815AF power system AC input BATT. LOAD1 LOAD2 LOAD3 LOAD4 1- 2- AC-L AC-N B1 B2 1- 2- BATT.(+) BATT.(-) LOAD(-) LOAD(+) Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 93 Used to set the rate of the serial port 6:ON 7:OFF supported The DIP switchs 1-5 are used to set the address of the environment monitoring module, Table shows the settings of the Dip switchs. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 94 Dip switchs. Table 7-8 Settings of the Dip switchs 6-7 Rate Value 4800bit/s 9600bit/s 19200bit/s Specifications Table 7-9 lists the specifications of the EPS75-4815AF power system. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 95 The sensor transfer box is an optional part. It provides diverse sensor ports to connect the monitoring unit to the sensors. Front Panel Figure 7-5 shows the PMIB01 sensor transfer box. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 96 JAC2 JAC1 FU_ALM JKM3 JKM2 JKM1 JKM4 JK 2 SIM2 SIM 1 JTP1 JTM1 SMOKE VTEM2 VBTEM2 JTD6 JTD7 JTD5 WATER TEM_HU JTD1 BAT_WE JTD4 JTD3 JTD2 Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 97 If no door-status sensor is used, connect pin 1 and pin 2 to disable door-status alarms. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 98 You can determine the type of signal to be accessed. With related configuration, the monitor unit can monitor them. Specifications Table 7-11 lists the specifications of the PMIB01 sensor transfer box. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 99: Pmib02 Sensor Transfer Box

    SIM1 SIM2 JTP1 JKM3 JKM4 F U _A LM JTM1 S M O K E V T E M 2 V B T E M 2 BAT WE WATER JTD7 JTD6 JTD5 Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 100 If no door-status sensor is used, connect pin 1 and pin 2 to disable door- status alarms. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 101 "JTD1-JTD7" are the input ports of the standby Boolean value. By default, the sensors are not configured. You can determine the type of signal to be accessed. With related configuration, the monitor unit can monitor them. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 102 EPMU02T, and from the EPMU02T to the control system are correct. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 103 JTM1 port of the sensor transfer box communication cable Monitoring cable of Temperature sensor of the BAT_WE terminal of the sensor the battery battery transfer box temperature sensor Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 104 Rear view of transfer box N-ESC PWR-ALM FAN-ALM TEST HWTB JTD1 JTD2 JTM1 HABA Partial enlarged drawing of ports PWR-ALM FAN-ALM TEST N-ESC View of fan backplane Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 105 EPMU02T, and from the EPMU02T to the control system are correct. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 106 To MDF monitoring module To equipment compartment and temperature control compartment door status sensors To HWCF STACK OUT To temperature and humidity sensor To battery temperature sensor Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 107 EPMU02T, and from the EPMU02T to the control system are correct. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 108 To equipment compartment and temperature control To HWTF compartment door STACK OUT status sensors To HWCF STACK OUT To temperature and To battery humidity sensor temperature sensor Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 109 Figure 7-13 shows the connections of environment monitoring cables in the F01D1000 cabinet. Table 7-18 describes the cable connections. By referring to the cable connection diagram, check Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 110 EPMU02T, and from the EPMU02T to the control system are correct. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 111 To HWTF compartment door STACK OUT status sensors To HWCF To smoke sensor STACK OUT To temperature and humidity sensor To battery temperature sensor Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 112 Monitoring cable of the battery Temperature sensor of the BAT_WE terminal of the temperature sensor battery sensor transfer box Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 113: Configuring The Environment Monitoring Parameters Of The Eps75-4815Af

    HABD defined defined a user- a user- shelf in the monitoring monitoring defined defined right digital digital monitoring monitoring device parameter parameter digital digital compartme parameter parameter Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 114 Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 115 The subnode ID must be the same as the subnode setting of the corresponding DIP switches on the EMU, but the subnode ID must be different from IDs of the other subnodes on the same bus. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 116 If the continuous float charging days duration of the rectifier unit exceeds the preset equalized charging interval, the battery enters the equalized charging state. Default: 60 days. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 117 This parameter is set according to the actual 44 V requirements. Default: 44 V. Battery set power-off This parameter is set according to the actual voltage: 43 V requirements. Default: 43 V. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 118 This parameter is set according to the actual requirements. Default: forbid. Battery auto-discharging This parameter is set according to the actual test period: 180d requirements. Default: 120d. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 119 10% RH requirements. When the actual humidity is equal to or lower than the lower alarm threshold, the system reports an alarm. Default: 10% RH. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 120 Valid level of digital When the low level represents the valid level, the parameter 5: low level host does not report an alarm in the case of low level. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 121 Configure the battery discharging test parameters Configure the rectifier unit parameter Configure the load and battery high-temperature power-off parameters Configure the environment monitoring parameters Configure the external extended digital parameters Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 122 The following considers the configuration in the F01D500 cabinet as an example to describe the process of configuring the environment monitoring parameters of the EPS75-4815AF. Log in to the PVM through the maintenance terminal and add an EMU. huawei(config)#emu add 0 POWER4875L 0 0 RS232 POWER4875L Issue 01 (2012-08-17) Huawei Proprietary and Confidential...
  • Page 123 The results show that the power, temperature, and humidity parameters have been configured automatically in the system; however, certain parameters need to be modified, and certain extended monitoring parameters need to be added. Configure the battery charging parameters. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 124 If the parameters need to be modified, run the power charge command. Configure the battery management parameters. huawei(config-if-power4875l-0)#power battery parameter 0.15 60 1 150 Configure the temperature compensation coefficient of the battery. If the planned data is the same as the query result, the parameters need not be configured.
  • Page 125 Load temperature off state : Normal ---------------------------------------------------------------------------- Name State |Name State Spare Dig0(Fan) Normal|Spare(HABF_FAN) Normal Spare Dig2 Normal|Spare Dig3(SPD) Normal Spare Dig4(Smoke) Normal|Spare Dig5(HEX) Alarm Spare Dig6(MDF-door) Alarm ---------------------------------------------------------------------------- Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 126 16. Save the data. huawei(config-if-power4875l-0)#quit huawei(config)#save 17. Close all doors of the cabinet. Then, query the alarm information again, and confirm that there is no alarm for any monitoring parameter. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 127: Etp4890 Monitoring Solution

    SMU01B, and from the SMU01B to the control system are correct. 8.4 Configuring the Environment Monitoring Parameters of the ETP4890 This topic describes how to configure the environment monitoring parameters of the ETP4890 through the CLI. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 128: Etp4890 Power System

    Appearance Figure 8-1 shows the appearance of the ETP4890 power system. Figure 8-1 ETP4890 power system Configuration Table 8-1 describes the components of the ETP4890 power system. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 129 19200 bit/s communicating with the upper device RS485/RS232 RS485/RS232 Baud rate: 9600 bit/s Used as a serial port, or 19200 bit/s supporting the northbound/ southbound communications Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 130 Table 8-5 Indicators on the monitoring module Indicator Color Status Description Green The monitoring module is faulty or there is no DC power input Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 131 The ETP4890 power system supports eight groups of output terminals. The left-side eight output terminals are negative and the right-side eight output terminals are positive. Figure 8-3 shows the output terminals in the ETP4890 power system. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 132 ETP4890 system. Figure 8-4 Output branch circuit breaker in the ETP4890 system Specifications Table 8-7 lists the specifications of the ETP4890 power system. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 133 442 mm x 255 mm x 86.1 mm x H) without brackets Weight ≤ 10 kg (including modules) Protection class IP20 Installation mode Installed in a IEC cabinet or an ETSI cabinet with brackets Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 134: Mue02A Sensor Transfer Box

    MUE02A sensor transfer box. Figure 8-5 Appearance of the MUE02A sensor transfer box Sensor Port Figure 8-6 Table 8-8 describe the sensor ports on the MUE02A sensor transfer box. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 135 Pin 2 is for the signal cable. VBTEM2 Port for detecting battery l Pin 1 is for the +12 V power temperature 2 supply. l Pin 2 is for the signal cable. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 136 MUE02A sensor transfer box. Table 8-9 Specifications of the MUE02A sensor transfer box Parameter Specifications Dimensions (H x W x D) 31 mm x 140 mm x 96 mm Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 137 SMU01B, and from the SMU01B to the control system are correct. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 138 One End Connects to... The Other End Connects to... Monitoring cable (1): J1 port of the sensor (1): DB50 port on the transfer box monitoring unit of the ETP4890 Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 139 SMU01B, and from the SMU01B to the control system are correct. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 140 UA5000 Universal Access Unit Environment Monitoring 8 ETP4890 Monitoring Solution Figure 8-8 Connections of environment monitoring cables in the F01D500 cabinet Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 141 Figure 8-9 shows the connections of environment monitoring cables in the F01D1000 cabinet. Table 8-12 describes the cable connections. By referring to the cable connection diagram, check Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 142 SMU01B, and from the SMU01B to the control system are correct. Figure 8-9 Connections of environment monitoring cables in the F01D1000 cabinet Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 143 VTEM2 terminal of the Temperature sensor temperature sensor sensor transfer box Monitoring cable of the battery VBTEM2 terminal of the Temperature sensor of the temperature sensor sensor transfer box battery Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 144: Configuring The Environment Monitoring Parameters Of The Etp4890

    Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 145 The battery is charged forcibly so as to quickly compensate for the lost capacity of the battery. floating: The battery adjusts charging/ discharging when it is in saturation. Default: automatic. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 146 Default: 65 AH. Temperature Upper temperature This parameter is set according to the actual compensatio threshold of the battery requirements. n parameter set: 80°C Default: 80°C. of the battery Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 147 AC undervoltage alarm. In this case, the rectifier unit powers off automatically to protect the system. Default: 180 V. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 148 Default: forbid. power-off parameters Battery high- This parameter is set according to the actual temperature power-off requirements. permission status: permit Default: forbid. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 149 The monitoring digital parameter of the fan tray is set here to monitor the fan tray. When the fan tray is faulty, the host reports an alarm. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 150 ETP4890 is configured correctly in the system. Figure 8-10 shows the configuration process, and Table 8-15 lists the commands used during the configuration. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 151 Configure the power supply load power off power-off and battery set power- off parameters Configure the power distribution power supply-parameter parameters Configure the battery power battery-test discharging test parameters Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 152 ETP4890 environment monitoring unit (EMU) is 3xxx and that of the EPS75-4815AF EMU is 1xxx. Log in to the PVM through the maintenance terminal and add an EMU. huawei(config)#emu add 0 POWER4875L 0 0 RS301 ETP4890 Query the status of the ETP4890. huawei(config)#display emu 0...
  • Page 153 If the parameters need to be modified, run the power charge command. Configure the battery management parameters. huawei(config-if-power4875l-0)#power battery parameter 0.15 60 1 150 Configure the temperature compensation coefficient of the battery. If the planned data is the same as the query result, the parameters need not be configured.
  • Page 154 11. Configure the load and battery high-temperature power-off parameters. huawei(config-if-power4875l-0)#power temperature-off load-off-state forbid load-off-temperature 70 battery-off-state permit battery-off-temperature 53 12. Configure the environment temperature parameters. huawei(config-if-power4875l-0)#power environment temperature 68 -5 80 -20 13. Configure the extended digital parameters. huawei(config-if-power4875l-0)#power outside_digital 0 available-level low- level name Fan...
  • Page 155 16. Save the data. huawei(config-if-power4875l-0)#quit huawei(config)#save 17. Close all doors of the cabinet. Then, query the alarm information again, and confirm that there is no alarm for any monitoring parameter. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 156: Fan Tray Monitoring Solution

    LED. 9.9 DIP Switches The fan tray is installed with a fan monitoring board. This topic describes the indications and settings of the DIP switches. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 157 9 Fan Tray Monitoring Solution 9.10 Configuring the Fan Environment Monitoring Parameters This topic describes how to configure the environment monitoring parameters through the command line interface (CLI). Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 158: Fan Tray Monitoring Principles

    Green: on for 1s and off for 1s The fan tray works in the normal state. repeatedly Green: on for 0.125s and off for The fan tray is faulty. 0.125s repeatedly Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 159: Dip Switch

    Sets the fan speed adjustment mode. By default, the fan speed is adjusted according to the temperature at the air SW101-8 exhaust vent. Table 9-3, Table 9-4, and Table 9-5 describe the settings of SW101. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 160 Reserved Method 3 Temperature at the air Method 4 intake vent (The fan stops rotating.) SW201 Table 9-6 describes the default settings of DIP switches of SW201. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 161 The fan tray works in the normal state. repeatedly Yellow: on for 1s and off for 1s The fan tray generates a warning that repeatedly does not affect the services. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 162 The default value of the address bit is 1. The fan tray communicates with the control board at a baud rate of 19200 bit/s. This is the default setting. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 163 HABD shelf Table 9-12 Settings of SW2-5 and SW2-6 SW2-6 SW2-5 Number of Fans Remarks In the UA5000, this item is mandatory. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 164 Speed Remarks Adjustment Mode Measuring the temperature of the air intake vent Measuring the In the UA5000, this item is temperature of the mandatory. air exhaust vent Reserved Measuring the temperature of the air intake vent when the fan stops rotating 9.6 LED...
  • Page 165 OFF: The connector is connected to a fan. DIP Switches of SW2 Table 9-16 describes the indications and default settings of the DIP switches of SW2. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 166 LED of the fan tray. Table 9-18 LED of the fan tray Status Description Green: on for 1s and off for 1s The fan tray works in the normal state. repeatedly Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 167: Dip Switches

    The three fans on the fan monitoring board of the HABM shelf are connected to corresponding connectors J1, J2, and J3 on the board. Table 9-20 describes the settings of SW1. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 168 Table 9-23 Settings of SW2-4 on the FCBA board SW2-4 Indication Default Setting The baud rate of the serial port is 19200 bit/ The baud rate of the serial port is 9600 bit/ Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 169: Configuring The Fan Environment Monitoring Parameters

    Alarm reporting Read temperature failure alarm: By default, the alarm reporting is for the fans permit enabled. Fan block alarm: permit Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 170 Add an EMU emu add Configure the fan speed adjustment mode fan_speed Configure the alarm reporting for the fans fan_alarmset Query the parameters of the fans display_fan_system_parameter Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 171 FAN timing mode: Auto timing ------------------------------------------------------------------ Alarm_name Permit/Forbid Read temperature fault Permit Fan block Permit Temperature high Permit Power fault Permit ------------------------------------------------------------------- Step 5 Save the data. huawei(config-if-fan-1)#quit huawei(config)#save ----End Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 172: Sensors

    10.2 Installing the Sensors This section describes how to install the sensors that are provided by Huawei. For those sensors not provided by Huawei, refer to their installation guide accordingly. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright ©...
  • Page 173: Sensor

    Temperatur 33010 ETP4830/ l Power supplied by ETP4830/ e sensor ETP4890 power ETP4890 power system. system l Temperature sensor with its own (F01D200, cable. F01D500, F01D1000) Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 174 H304ESC 33010 front access (F02AF) (phot l EPS30-4815 oelect ric) EPS75-4815 Temperature power system (F02A, F02AF, M200, F01D200, F01D500, and F01D1000) Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 175: Temperature And Humidity Sensor

    The signals output by the external temperature and humidity sensor generally are the standard current analog output (4 mA-20 mA). Appearance Figure 10-1 shows the temperature and humidity sensor. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 176 Storage -40°C to 60°C (not condensing) temperature Shell material ABS engineering plastic 1. Q: Why is the temperature reported by the EMU higher than the actual temperature? Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 177: Door Status Sensor

    In general, the temperature sensor and the humidity sensor are integrated together in Huawei. The integrated sensor may be installed at the top of the cabinet. Since the temperature at the exhaust vent is higher than the actual temperature, the relative humidity of that area will become lower.
  • Page 178: Smoke Sensor

    The smoke sensor is sensitive to the white smoke that is generated in burning. The smoke sensor can prompt the fire in advance. Figure 10-3 shows the smoke sensor. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 179 Table 10-5 Technical specifications of the smoke sensor Parameter Value Type JTY-GD-S839 Power supply voltage 24 VDC ± 5% Output type 2-wire Boolean value type Operating type Optical or electrical smoke sensing type Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 180: Water Sensor

    The water sensor is used to monitor the liquid level change. Appearance The liquid-level sensor adopted by Huawei is a kind of plug-in spacing liquid-level sensor. This sensor is of the current type. When the sensor enters the liquid, the power supply forms an injection current to the signal end so as to monitor the liquid level change.
  • Page 181: Mdf Sensor

    MDF contains the cable side terminal blocks, exchange side terminal blocks, and protective units. To detect the MDF status is to detect the status of the protective units. Figure 10-6 shows the MDF. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 182: Surge Protector Sensor

    The surge protector has the over-voltage protection function against lightning. It can protect the power supply device and the powered devices. The following uses SPD27SZ as an example. Figure 10-7 Figure 10-8 show the appearance of the SPD27SZ surge protector. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 183 UA5000 Universal Access Unit Environment Monitoring 10 Sensors Figure 10-7 Cover of the SPD27SZ surge protector Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 184 Diesel input First-level Second-level Lout Mains Decouplin protection protection input g circuit Nout circuit circuit Breaker Power cable Cables Signal cable PE cable Control cable Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 185: Battery Temperature Sensor

    Do not connect the temperature probe to other heating devices. There is a separate BOM for the battery temperature sensor. Figure 10-10 shows the appearance of the battery temperature sensor. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 186: Hx02-22Sh Heat Exchanger

    This topic provides the appearance and specifications of the HX02-22SH heat exchanger, and describes the functions and working principles of the heat exchanger. Appearance Figure 10-11 shows the appearance of the HX02-22SH heat exchanger. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 187 Figure 10-12 illustrates the working principles of the HX02-22SH heat exchanger. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 188 Green: on The AC or DC power is available. Green: on for 1s and off for 1s The heat exchanger is running repeatedly in the normal state. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 189: Hx03T-22Sh Heat Exchanger

    This topic provides the appearance of the HX03T-22SH heat exchanger, describes the functions and working principles of it, and lists parameters of it. Appearance Figure 10-13 shows the appearance of the HX03T-22SH heat exchanger. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 190 The HX03T-22SH heat exchanger is used to cool the air inside a sealed cabinet by exchanging heat with environment air. Figure 10-14 illustrates the working principles of the HX03T-22SH heat exchanger. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 191 The AC or DC power is on. indicates the Green: on for 1s and off for 1s The heat exchanger is running power status repeatedly in the normal state. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 192: Hx03E-22Sh Heat Exchanger

    This topic provides the appearance of the HX03E-22SH heat exchanger, describes the functions and working principles of it, and lists parameters of it. Appearance Figure 10-15 shows the appearance of the HX03E-22SH heat exchanger. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 193 Figure 10-16 illustrates the working principles of the HX03E-22SH heat exchanger. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 194 The AC or DC power is on. indicates the Green: on for 1s and off for 1s The heat exchanger is running power status repeatedly in the normal state. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 195: Sensors Selected By Users

    Output type of the humidity signal: current type (4 mA to 20 mA) Temperature measurement range: -20°C to +80°C Humidity measurement range: 0% RH to 100% RH Figure 10-17 shows the relation between the temperature and output current. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 196 Figure 10-18 Relation between the humidity and output current Humidity 100% RH 0% RH 20 mA 4 mA Current Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 197 Table 10-16 Specifications of the output signal types Specification Smoke Sensor Type No smoke is detected. Smoke is detected. Current type Output current < 200 uA Output current > 1 mA Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 198: Installing The Sensors

    Disconnected Connected 10.2 Installing the Sensors This section describes how to install the sensors that are provided by Huawei. For those sensors not provided by Huawei, refer to their installation guide accordingly. 10.2.1 Installation Position This topic describes the installation positions of sensors.
  • Page 199: Installation Preparation

    This section describes the context, precautions and procedure for installing the temperature and humidity sensor. Context The requirements for installing the temperature and humidity sensor are as follows: Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 200 In the above figures, JTAx refers to the analog parameter port on the ESC, which is determined by the main label on the monitoring cable. Insert the monitoring cable to the corresponding analog port. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 201: Installing The Door Status Sensor

    This section describes how to install the door status sensor. Context The requirements for installing the door status sensor are as follows: The door gap shall be less than 5 mm when the doors are closed. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 202: Installing The Smoke Sensor

    – Only black smoke is generated in burning, and no smoke or little smoke is generated. – The relative humidity is larger than 95% for a long period. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 203 Figure 10-22 Structure of the auxiliary base Table 10-19 Dimensions of the smoke sensor base Dimension Specification Outline (W x D x H) 75mm×51mm×5mm Fixing hole 5mm×10mm Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 204 Figure 10-23 Installing the smoke sensor Step 3 Connect the sensor cable. Figure 10-24 shows the connections of the smoke sensor. Figure 10-24 Connections of the smoke sensor Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 205: Installing The Water Sensor

    Ensure that the solid-state liquid-level sensing head faces upward. Figure 10-25 shows how to install the water sensor. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 206 Figure 10-26 Connections of the water sensor Cable: 04025177 (including water sensor) Main label 1. +24 VDC 2. +12 VDC 3. Signal input 4. GND JTDx Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 207: Installing The Mdf Sensor

    To detect the MDF status is to detect the status of the protective units. Procedure Step 1 Connect the sensor cable. Figure 10-29 shows the connections of the MDF. Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 208: Installing The Surge Protector Sensor

    Step 1 Connect the sensor cable. Figure 10-30 shows the connections for the status monitoring of the SPD27SZ surge protector. Figure 10-30 Connections of the SPD27SZ the surge protector ----End Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 209: Installing The Battery Temperature Sensor

    Step 2 The other end is the temperature probe with a ring terminal, which is bundled with the negative lead of a single battery, as shown in Figure 10-31. Figure 10-31 Connection of the battery temperature sensor ----End Issue 01 (2012-08-17) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.

Table of Contents