UA5000 Universal Access Unit V100R019C06 Environment Monitoring Issue Date 2012-08-17 HUAWEI TECHNOLOGIES CO., LTD.
Page 2
All other trademarks and trade names mentioned in this document are the property of their respective holders. Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope.
Page 27
The following considers the configuration in the F02A cabinet as an example to describe the process of configuring the environment monitoring parameters of the H303ESC board. Log in to the UA5000 through the maintenance terminal and add an EMU. huawei(config)#emu add 0 H303ESC 0 30 rs232 H303ESC Query the status of the H303ESC board.
Page 28
The results show that certain monitoring parameters, such as temperature, humidity, door status, and MDF, have been configured automatically in the system. Other monitoring parameters, however, need to be configured manually. Configure the analog parameters. huawei(config-if-h303esc-0)#esc analog 0 alarm-upper-limit 50 alarm-lower- limit 10 huawei(config-if-h303esc-0)#esc analog 1 alarm-upper-limit 80 alarm-lower- limit 5...
Page 47
H304ESC board. Log in to the UA5000 through the maintenance terminal and add an EMU. huawei(config)#emu add 0 H304ESC 0 30 rs232 H304ESC Query the status of the H304ESC board.
Page 48
5 alarm-upper-limit 80 alarm-lower- limit 0 name Humidity sensor-type 0:voltage analog-alarm 2 unit %RH Configure the digital parameters. huawei(config-if-h304esc-0)#esc digital 2 available-level low-level name SPD1 huawei(config-if-h304esc-0)#esc digital 3 available-level low-level name SPD2 huawei(config-if-h304esc-0)#esc digital 4 available-level low-level name SW1...
Page 62
The following considers the configuration in the M200 cabinet as an example to describe the process of configuring the environment monitoring parameters of the ESCM. Log in to the UA5000 through the maintenance terminal and add an EMU. huawei(config)#emu add 0 MiniESC 0 30 rs232 MiniESC Enter the ESCM configuration mode and query the default analog and digital parameters.
Page 63
2 alarm-upper-limit 80 alarm-lower- limit 0 name Humidity sensor-type 0:voltage analog-alarm 2 unit %RH Configure the digital parameters. huawei(config-if-MiniESC-0)#esc digital 9 available-level low-level name szl9 digital-alarm Query the default configuration of the analog and digital parameters. huawei(config-if-MiniESC-0)#display esc environment info...
Page 84
The following considers the configuration in the F01E400 cabinet as an example to describe the process of configuring the environment monitoring parameters of the EPS30-4815AF. Log in to the UA5000 through the maintenance terminal and add an EMU. huawei(config)#emu add 0 POWER4845 0 0 RS232 POWER4830 Query the status of the EPS30-4815AF.
Page 85
If the planned data is the same as the query result, the parameters need not be configured. If the parameters need to be modified, run the power charge command. Configure the battery management parameters. huawei(config-if-power4845-0)#power battery parameter 0.15 60 1 75 Configure the temperature compensation coefficient of the battery. huawei(config-if-power4845-0)#power battery temperature 80 -20 80 Configure the power supply load power-off and battery set power-off parameters.
Page 122
The following considers the configuration in the F01D500 cabinet as an example to describe the process of configuring the environment monitoring parameters of the EPS75-4815AF. Log in to the PVM through the maintenance terminal and add an EMU. huawei(config)#emu add 0 POWER4875L 0 0 RS232 POWER4875L Issue 01 (2012-08-17) Huawei Proprietary and Confidential...
Page 124
If the parameters need to be modified, run the power charge command. Configure the battery management parameters. huawei(config-if-power4875l-0)#power battery parameter 0.15 60 1 150 Configure the temperature compensation coefficient of the battery. If the planned data is the same as the query result, the parameters need not be configured.
Page 152
ETP4890 environment monitoring unit (EMU) is 3xxx and that of the EPS75-4815AF EMU is 1xxx. Log in to the PVM through the maintenance terminal and add an EMU. huawei(config)#emu add 0 POWER4875L 0 0 RS301 ETP4890 Query the status of the ETP4890. huawei(config)#display emu 0...
Page 153
If the parameters need to be modified, run the power charge command. Configure the battery management parameters. huawei(config-if-power4875l-0)#power battery parameter 0.15 60 1 150 Configure the temperature compensation coefficient of the battery. If the planned data is the same as the query result, the parameters need not be configured.
Page 154
11. Configure the load and battery high-temperature power-off parameters. huawei(config-if-power4875l-0)#power temperature-off load-off-state forbid load-off-temperature 70 battery-off-state permit battery-off-temperature 53 12. Configure the environment temperature parameters. huawei(config-if-power4875l-0)#power environment temperature 68 -5 80 -20 13. Configure the extended digital parameters. huawei(config-if-power4875l-0)#power outside_digital 0 available-level low- level name Fan...
Page 164
Speed Remarks Adjustment Mode Measuring the temperature of the air intake vent Measuring the In the UA5000, this item is temperature of the mandatory. air exhaust vent Reserved Measuring the temperature of the air intake vent when the fan stops rotating 9.6 LED...
In general, the temperature sensor and the humidity sensor are integrated together in Huawei. The integrated sensor may be installed at the top of the cabinet. Since the temperature at the exhaust vent is higher than the actual temperature, the relative humidity of that area will become lower.
The water sensor is used to monitor the liquid level change. Appearance The liquid-level sensor adopted by Huawei is a kind of plug-in spacing liquid-level sensor. This sensor is of the current type. When the sensor enters the liquid, the power supply forms an injection current to the signal end so as to monitor the liquid level change.
Disconnected Connected 10.2 Installing the Sensors This section describes how to install the sensors that are provided by Huawei. For those sensors not provided by Huawei, refer to their installation guide accordingly. 10.2.1 Installation Position This topic describes the installation positions of sensors.