Huawei UA5000 Manual page 120

Environment monitoring
Hide thumbs Also See for UA5000:
Table of Contents

Advertisement

UA5000 Universal Access Unit
Environment Monitoring
Item
External
extended
digital
parameters
Issue 01 (2012-08-17)
Data Plan for the
F01D500 Cabinet
Digital parameter ID: 0
Valid level of digital
parameter 0: low level
Digital parameter ID: 1
Valid level of digital
parameter 1: low level
Digital parameter ID: 3
Valid level of digital
parameter 3: low level
Digital parameter ID: 4
Valid level of digital
parameter 4: high level
Digital parameter ID: 5
Valid level of digital
parameter 5: low level
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7 EPS75-4815AF Monitoring Solution
Remarks
This digital parameter is set according to the
actual requirements. The monitoring digital
parameter of the fan tray is set here to monitor the
fan tray. When the fan tray is faulty, the host
reports an alarm.
When the low level represents the valid level, the
host does not report an alarm in the case of low
level.
This digital parameter is set according to the
actual requirements. The monitoring digital
parameter of the fan tray is set here to monitor the
fan tray. When the fan tray is faulty, the host
reports an alarm.
When the low level represents the valid level, the
host does not report an alarm in the case of low
level.
This digital parameter is set according to the
actual requirements. The monitoring digital
parameter of the surge protector is set here to
monitor the status of the surge protector. When
the surge protector is faulty, the host reports an
alarm.
When the low level represents the valid level, the
host does not report an alarm in the case of low
level.
This digital parameter is set according to the
actual requirements. The monitoring digital
parameter of the smoke sensor is set here to
monitor whether there is smoke in the actual
environment. When there is smoke, the host
reports an alarm.
When the high level represents the valid level, the
host does not report an alarm in the case of high
level.
This digital parameter is set according to the
actual requirements. The monitoring digital
parameter of the heat exchanger is set here to
monitor the status of the heat exchanger. When
the heat exchanger is faulty, the host reports an
alarm.
When the low level represents the valid level, the
host does not report an alarm in the case of low
level.