Environment monitoring
Hide thumbs Also See for UA5000:
Table of Contents

Advertisement

UA5000 Universal Access Unit
Environment Monitoring
To...
Configure the analog
parameters
Configure the digital
parameters
The following considers the configuration in the F02A cabinet as an example to describe the
process of configuring the environment monitoring parameters of the H303ESC board.
1.
2.
3.
Issue 01 (2012-08-17)
Log in to the UA5000 through the maintenance terminal and add an EMU.
huawei(config)#emu add 0 H303ESC 0 30 rs232 H303ESC
Query the status of the H303ESC board.
huawei(config)#display emu 0
EMU ID: 0
----------------------------------------------------------------------------
EMU name
: H303ESC
EMU type
: H303ESC
Used or not : Used
EMU state
: Normal
Frame ID
: 0
Subnode
: 30
COM port
: RS232
----------------------------------------------------------------------------
Enter the H303ESC configuration mode and query the default analog and digital
parameters.
huawei(config)#interface emu 0
huawei(config-if-h303esc-0)#display esc system parameter
EMU ID: 0
----------------------------------------------------------------------------
FAN run mode: Auto
C
AnalogID Name
0
Temperature
1
Humidity
2
-
3
-
4
-
5
-
6
-
7
-
----------------------------------------------------------------------------
DigitalID Name
0
Wiring
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Run the Command...
esc analog
IDs of user-defined alarms in the analog parameters: IDs 1-4
are reserved alarm IDs in the system (1: temperature; 2:
humidity; 3: voltage; 4: current), and IDs 5-20 are alarm IDs
allocated to other user-defined alarms by users.
esc digital
IDs of user-defined alarms in the digital parameters: IDs 1-20
are reserved alarm IDs in the system (1: AC_voltage; 2:
AC_switch; 3: Battery_voltage; 4: Battery_fuse; 5:
Load_fuse; 6: Rectifier; 7: DC_power; 8: Cupboard_door; 9:
Room_door; 10: Window; 11: Theft; 12: Wiring; 13: Fan; 14:
Fire; 15: Fog; 16: Water; 17: Diesel; 18: Smell 19:
Air_conditioner; 20: SPD), and IDs 21-52 are alarm IDs
allocated to other user-defined alarms by users.
ESC system parameter
Auto open temperature: 45 C
AlmUpper AlmLower TestUpper TestLower Unit
55
5
80
0
127
-128
127
-128
127
-128
127
-128
127
-128
127
-128
Level
|DigitalID Name
1
|
1
3 H303ESC Monitoring Solution
Auto close temperature: 30
100
-27
C
100
0
%R.H.
127
-128
-
127
-128
-
127
-128
-
127
-128
-
127
-128
-
127
-128
-
Door0
Type
Voltage
Voltage
Voltage
Voltage
Voltage
Voltage
Voltage
Voltage
Level
0
21