UA5000 Universal Access Unit
Environment Monitoring
Table 5-3 Settings of SW1
Electrical
Switch
SW1-1 to
SW1-4
SW1-5
SW1-6
SW1-7
SW1-8
When the ESCM EMU adopts the RS-485 communication mode, SW1-1 to SW1-4 are used to
set the address of the environment monitoring board.
SW1-4.
Table 5-4 Settings of SW1-1 to SW1-4
SW1-4
0
0
0
0
0
0
0
0
Issue 01 (2012-08-17)
Setting
Indication
Supported
Used to set the address of the
environment monitoring board.
Not
-
supported
ON
The rate of the serial port is 19200
bit/s.
OFF
The rate of the serial port is 9600 bit/
s.
ON
The external sensor of JTA1 is of the
current type.
OFF
The external sensor of JTA1 is of the
voltage type.
ON
The external sensor of JTA2 is of the
current type.
OFF
The external sensor of JTA2 is of the
voltage type.
SW1-3
SW1-2
0
0
0
0
0
1
0
1
1
0
1
0
1
1
1
1
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 ESCM Monitoring Solution
Factory Default
SW1-1: ON
SW1-2: ON
SW1-3: OFF
SW1-4: OFF
ON
OFF
ON
ON
Table 5-4
shows the settings of SW1-1 to
SW1-1
Address Value
0
0
1
1
0
2
1
3
0
4
1
5
0
6
1
7
49