Huawei UA5000 Manual page 45

Environment monitoring
Hide thumbs Also See for UA5000:
Table of Contents

Advertisement

UA5000 Universal Access Unit
Environment Monitoring
Item
Issue 01 (2012-08-17)
Data
Digital parameter ID: 6
Valid level of digital
parameter 6: low level
Digital parameter ID: 8
Valid level of digital
parameter 8: low level
Digital parameter ID: 9
Valid level of digital
parameter 9: low level
Digital parameter ID: 10
Valid level of digital
parameter 10: low level
Digital parameter ID: 11
Valid level of digital
parameter 11: low level
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4 H304ESC Monitoring Solution
Remarks
The monitoring digital parameter of SW3 is
set here to monitor the status of SW3. When
SW3 is turned off, the host reports an alarm.
When the low level represents the valid level,
the host does not report an alarm in the case
of low level.
The monitoring digital parameter of the fans
of the master HABD shelf is set here to
monitor the status of the fans of the master
HABD shelf. When the fan tray is faulty, the
host reports an alarm.
When the low level represents the valid level,
the host does not report an alarm in the case
of low level.
The monitoring digital parameter of the fans
of the HABF shelf connected to the master
HABD shelf is set here to monitor the status
of the fans of the HABF shelf. When the fan
tray is faulty, the host reports an alarm.
When the low level represents the valid level,
the host does not report an alarm in the case
of low level.
The monitoring digital parameter of the fans
of the HABD shelf subtended to the master
HABD shelf is set here to monitor the status
of the fans of the HABD shelf. When the fan
tray is faulty, the host reports an alarm.
When the low level represents the valid level,
the host does not report an alarm in the case
of low level.
The monitoring digital parameter of the fans
of the HABF shelf connected to the
subtended HABD shelf is set here to monitor
the status of the fans of the HABF shelf.
When the fan tray is faulty, the host reports
an alarm.
When the low level represents the valid level,
the host does not report an alarm in the case
of low level.