Huawei UA5000 Manual page 34

Environment monitoring
Hide thumbs Also See for UA5000:
Table of Contents

Advertisement

UA5000 Universal Access Unit
Environment Monitoring
DIP switch S2 is used to set the type of external analog sensors.
and settings of S2 on the H304ESC.
Table 4-4 Setting of S2 on the H304ESC
DIP Switch
S2-1
S2-2
S2-3
S2-4
DIP switch S3 is used to set the reporting mode and rate.
on the H304ESC.
Table 4-5 Settings of S3 on the H304ESC
DIP Switch
S3-1
S3-2
S3-3
S3-4
S3-5 to S3-8
Issue 01 (2012-08-17)
Setting
Meaning
ON
The external sensor of JTA1 is of the
current type
OFF
The external sensor of JTA1 is of the
voltage type
ON
The external sensor of JTA2 is of the
current type
OFF
The external sensor of JTA2 is of the
voltage type
ON
The external sensor of JTA3 is of the
current type
OFF
The external sensor of JTA3 is of the
voltage type
Reserved
Unavailable
Setting
Meaning
ON
The H304ESC is used in the access network
OFF
The H304ESC is used in the exchange
ON
The H304ESC uses one serial port for
reporting
OFF
The H304ESC uses two serial ports for
reporting
Reserved
Unavailable
ON
The reporting rate of the serial port is 19200
bit/s
OFF
The reporting rate of the serial port is 9600 bit/
s
Reserved
Unavailable
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4 H304ESC Monitoring Solution
Table 4-4
describes the meanings
Default
Setting
OFF
OFF
OFF
-
Table 4-5
describes the settings of S3
Default
Setting
ON
OFF
-
OFF
-
28