COM ID
Command BaudRate
0
-
-
1
-
-
PowerNumber
: 0
----------------------------------------------------------------------------
The results show that certain monitoring parameters, such as temperature, humidity, door
status, and MDF, have been configured automatically in the system. Other monitoring
parameters, however, need to be configured manually.
Configure the analog parameters.
huawei(config-if-h303esc-0)#esc analog 0 alarm-upper-limit 50 alarm-lower-
limit 10
huawei(config-if-h303esc-0)#esc analog 1 alarm-upper-limit 80 alarm-lower-
limit 5
huawei(config-if-h303esc-0)#esc analog 4 alarm-upper-limit 75 alarm-lower-
limit 45 name Supply_Voltage sensor-type 0:voltage analog-alarm 3 unit Volt
Configure the digital parameters.
huawei(config-if-h303esc-0)#esc digital 2 available-level low-level digital-
alarm 13 name fan1
huawei(config-if-h303esc-0)#esc digital 3 available-level low-level digital-
alarm 13 name fan2
huawei(config-if-h303esc-0)#esc digital 4 available-level low-level digital-
alarm 13 name fan3
huawei(config-if-h303esc-0)#esc digital 5 available-level low-level digital-
alarm 13 name fan4
Query the environment information, and confirm that the environment monitoring
functions are normal and the door status alarm other than alarms for other monitoring
parameters is generated.
huawei(config-if-h303esc-0)#display esc environment info
EMU ID: 0
FAN control mode :Auto
---------------------------Analog environment info--------------------------
ID Name
0
Temperature
1
Humidity
2
-
3
-
4
Supply_Voltage
5
6
-
7
-
---------------------------Digital environment
info---------------------------
ID Name
0
Wiring
2
fan1
4
fan3
6
-
8
-
10 -
12 -
14 -
16 -
18 -
20 -
----------------------------------------------------------------------------
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
1
|
3
1
|
5
1
|
7
1
|
9
1
|
11
1
|
13
1
|
15
1
|
17
1
|
19
1
|
21
DataLength
StopLength
-
-
-
-
PowerType
: -
ESC environment state
FAN run state: Open
State
Value
AlmUpper
Normal
29.00
50
Normal
30.98
80
Normal
-128.00
127
Normal
-128.00
127
Normal
53.50
75
Normal
-128.00
127
Normal
-128.00
127
Normal
-128.00
127
State
Value |ID Name
Normal 1
|1
Door0
Normal 0
|3
fan2
Normal 0
|5
fan4
Normal 1
|7
-
Normal 1
|9
-
Normal 1
|11 -
Normal 1
|13 -
Normal 1
|15 -
Normal 1
|17 -
Normal 1
|19 -
Normal 1
|21 -
3 H303ESC Monitoring Solution
-
-
-
-
-
-
-
-
-
-
ParityType
-
-
AlmLower
Unit
10
C
5
%R.H.
-128
-
-128
-
45
-
-128
-
-128
-
-128
-
State
Value
Alarm
1
Normal 0
Normal 0
Normal 1
Normal 1
Normal 1
Normal 1
Normal 1
Normal 1
Normal 1
Normal 1
1
1
1
1
1
1
1
1
1
1
22