The following tables show parameters and default settings that change with the drive model selection (o2-04). Parameter
numbers shown in parenthesis are valid for motor 2.
Table 1.4 2.4 kV Class Drives Default Settings by Drive Model Selection
No.
Name
<61>
Model
CIMR-MV2
Drive Model
o2-04
Selection
E2-11(E4-11)
Motor Rated Power kW
V/f Gain during Speed
b3-04
Search
Output Current 1 during
b3-06
Speed Search
Speed Search Method
b3-11
Switching Level (Speed
Estimate Speed Search)
E2-01(E4-01)
Motor Rated Current
E2-02(E4-02)
Motor Rated Slip
E2-03(E4-03) Motor No-Load Current
Motor Line-to-Line
E2-05(E4-05)
Resistance
Motor Leakage
E2-06(E4-06)
Inductance
Motor Iron Loss for
E2-10(E4-10)
Torque Compensation
Momentary Power Loss
L2-02
Ride-Thru Time
Momentary Power Loss
L2-03
Minimum Baseblock
Time
Momentary Power Loss
L2-04
Voltage Recovery Time
Undervoltage Detection
L2-05
Level (Uv)
L8-02
Overheat Alarm Level
<62>
Output Ground Fault
L8-09
Detection Selection
FAN Board Use
L8-33
Selection
Transformer Overheat
L8-87
Alarm (TMA) Level
Transformer Overheat
L8-88
Fault (TME) Level
Hunting Prevention Time
n1-03
Constant
Output Current Detection
n9-02
Gain
Input Current
n9-71
Conversion Coefficient
Reference Voltage for
o2-11
Input Voltage Detection
<61> Parameter numbers shown in parenthesis are valid for motor 2.
<62> The alarm detection level differs for each drive model because of the different thermistor position on each drive.
82
Unit
052 058 077 093 102 115 135 160 180 205 220 330 390 440 505 550 600
00
01
02
03
170 190 260 310 340 380 450 530 600 680 730 1100 1300 1460 1680 1830 2000
%
80
80
80
80
0.5
0.5
0.5
0.5
%
5.0
5.0
5.0
5.0
A
40.0 50.0 70.0 80.0 90.0 100.0 110.0 140.0 150.0 170.0 190.0 280.0 330.0 370.0 430.0 470.0 510.0
Hz
0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25
A
10.0 13.0 18.0 20.0 23.0 25.0 28.0 35.0 38.0 43.0 48.0 70.0 83.0 93.0 108.0 118.0 128.0
W
0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300
%
20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0
W
0
0
0
0
sec
2.0
2.0
2.0
2.0
sec
10.0 13.0 18.0 20.0 23.0 25.0 28.0 35.0 38.0 43.0 48.0 70.0 83.0 93.0 108.0 118.0 128.0
sec
3.0
3.0
3.0
3.0
V
693
693
693
693
105
105
105
105
1
1
1
1
1
1
1
1
°C
100
100
100
100
°C
140
140
140
140
ms
30
30
30
30
1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000
0.0235 0.0235 0.0150 0.0150 0.0150 0.0094 0.0094 0.0060 0.0060 0.0060 0.0060 0.0044 0.0030 0.0020 0.0020 0.0020 0.0020
V
2400 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400
Default Settings
04
05
06
07
08
80
80
80
80
80
0.5
0.5
0.5
0.5
0.5
0.5
5.0
5.0
5.0
5.0
5.0
5.0
0
0
0
0
0
2.0
2.0
2.0
2.0
2.0
2.0
3.0
3.0
3.0
3.0
3.0
3.0
693
693
693
693
693
693
105
105
105
105
105
105
1
1
1
1
1
1
1
1
2
2
100
100
100
100
100
100
140
140
140
140
140
140
30
30
30
30
30
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
09
0A
0C
0D
0E
0F
80
80
80
80
80
80
0.5
0.5
0.5
0.5
0.5
5.0
5.0
5.0
5.0
5.0
0
0
0
0
0
2.0
2.0
2.0
2.0
2.0
3.0
3.0
3.0
3.0
3.0
693
693
693
693
693
95
105
105
105
105
1
1
1
1
1
2
2
2
2
2
100
100
100
100
100
140
140
140
140
140
30
30
30
30
30
30
10
11
80
80
0.5
0.5
5.0
5.0
0
0
0
2.0
2.0
3.0
3.0
693
693
105
105
1
1
1
2
2
2
100
100
140
140
30
30

Advertisement

Table of Contents
loading