Avaya 9012FC IO Manual page 33

Installing cooling modules for virtual services platform 9000
Table of Contents

Advertisement

Modules on the VSP
9012
Second generation I/O module sensors
Inlet and outlet sensors
Field Programmable Gate
Array (FPGA) sensors
Fabric Adapter (FA)
sensors
Bringing the module online
If a module shuts down due to heat, you must intervene to bring the slot back online. After you
correct the temperature issue and the heat condition clears, you must bring the module back online.
The module does not go online again unless you re-enable the module. After CP, SF, or I/O
modules shut down, use the sys power slot {slot[-slot][,...]} command to bring the
module back online.
Fan speed
The cooling module fan speed increases as the temperature reading of the sensors increases. The
cooling module fan speed decreases as the temperature reading of the sensors decreases.
System temperature information
Each of the zones correspond to temperature sensors on the modules. For instance, the I/O module
has five temperature zones. Zones 1, 2, and 3 are inlet air sensors and 4 and 5 are outlet air
sensors. The SF module has two temperature sensors and the CP module has four temperature
March 2015
Module LED color
Blinking red
Green
Blinking red
Green
Blinking red
Green
Comments? infodev@avaya.com
Virtual Services Platform 9012
Alarm threshold
69 °C
At 70 °C, the system
triggers the alarm when
the module exceeds the
alarm threshold by one
degree.
Alarm clears after the
temperatures of the
modules are at 68 °C.
90 °C
At 91 °C, the system
triggers the alarm when
the module exceeds the
alarm threshold by one
degree.
Alarm clears after the
temperatures of the
modules are at 89 °C.
105°C
At 106°C, the system
triggers the alarm when
the module exceeds the
alarm threshold by one
degree.
Alarm clears after the
temperatures of the
modules are at 104°C.
Installing Cooling Modules in Avaya VSP 9000
Shutdown threshold
74 °C
At 75 °C, the system
shuts down the module
when the module
exceeds the shutdown
threshold by one degree.
95 °C
At 96 °C, the system
shuts down the module
when the module
exceeds the shutdown
threshold by one degree.
110°C
At 111°C, the system
shuts down the module
when the module
exceeds the shutdown
threshold by one degree.
33