Mechanical Stability In Operation; Product Group Xr-300M Poe; Approvals; Xr-300M Poe Approvals, Certificates - Siemens SCALANCE X-300 Series Operating Instructions Manual

Industrial ethernet switches
Hide thumbs Also See for SCALANCE X-300 Series:
Table of Contents

Advertisement

Note
Shipbuilding approval
You will find shipbuilding approvals on the Internet on the pages of Siemens Industry
Automation Customer Support under the following entry ID:
33118441 (http://support.automation.siemens.com/WW/view/en/33118441)
"Entry list" tab > entry type "Certificates"
11.6.1.4

Mechanical stability in operation

The switch meets the following requirements for mechanical stability:
IEC 60068-2-6 (vibration)
● Securing on a DIN rail
5 – 9 Hz: 3.5 mm
9 – 150 Hz: 1 g
1 octave/min, 20 sweeps
IEC 60068-2-27 (shock)
● Securing on a DIN rail
15 g, 11 ms duration, 6 shocks per axis
11.7

Product group XR-300M PoE

11.7.1

Approvals

11.7.1.1

XR-300M PoE approvals, certificates

Approvals issued
Note
Issued approvals on the type plate of the device
The specified approvals apply only when the corresponding mark is printed on the product. You
can check which of the following approvals have been granted for your product by the markings
on the type plate.
SCALANCE X-300
Operating Instructions, 11/2019, A5E01113043-24
Certifications and approvals
11.7 Product group XR-300M PoE
285