1.2
General Description
u
A1000 Model Selection
Refer to
Table 1.1
for drive selection depending on the motor power and Normal or Heavy Duty rating.
Note: The models and capacities in shown here are based on standard settings and operation conditions. Higher carrier frequencies and higher ambient
temperatures require derating.
Motor Power (kW)
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
<1> These values assume the carrier frequency is not set higher than 8 kHz.
<2> These values assume the carrier frequency is set to 2 kHz.
Note: Current derating is required when setting the carrier frequency higher.
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Table 1.1 A1000 Models
Heavy Duty Rating
Model CIMR-Ao
5A0003
5A0004
5A0006
5A0009
5A0011
5A0017
5A0022
5A0027
5A0032
–
Three-Phase 600 V Class
Rated Output
Model CIMR-Ao
<1>
Current (A)
1.7
3.5
4.1
6.3
9.8
12.5
17
22
27
–
Refer to Carrier Frequency Derating on page 377
1.2 General Description
Normal Duty Rating
Rated Output
Current (A)
–
5A0003
5A0004
5A0006
5A0009
5A0011
5A0017
5A0022
5A0027
5A0032
<2>
–
2.7
3.9
6.1
9
11
17
22
27
32
for details.
1
29