Product Specifications - Delta DFM-400P Installation & Application Manual

Delta field module (4 pulse inputs)
Table of Contents

Advertisement

DFM-400P Rev 2.1 Installation and Appplication Guide Edition 1.6

Product Specifications

Power Requirements
24 VAC
2 VA
Class II
Ambient Ratings
32º to 131º F (0º to 55º C)
10 to 90% RH (non-condensing)
Communication Ports
NET1 – RS-485 LAN
BACnet MS/TP Connection Only (LINKnet is not supported)
Autobaud Communications Speed @ 9,600 or 19,200 or 38,400 or 76,800 bps
Maximum of 99 nodes per MS/TP segment (50 without a repeater)
Service Port
RJ-11 Jack for Delta Service Tool devices such as CON-768BT
Inputs
2 Pulse Inputs (PP1 and PP2) @ 0 - 2000 Hz each (or actual maximum of about 1950)
2 Pulse Inputs (PP3 and PP4) @ 0 - 200 Hz each
Monitors either Dry Contact or Open Collector signals
Jumper selectable DEBOUNCE circuitry for mechanical contacts for pulses less than 200
Hz
Technology
8-bit Processor c/w internal A/D, Flash, and RAM
Software Clock
Visual LED status indication of the CPU
Device Addressing
Set via DIP switch, or Software Setup
DIP switch MAC Address Range: 0 to 99 per network segment
Software Address Range: As per the BACnet standard
Supports DNA – Delta's intuitive addressing scheme
Size
Controller & Enclosure
5.4" x 4.2" x 1.9" (13.6 cm x 10.7 cm x 4.9 cm)
Weight including Enclosure
0.384 lb. (179 g.)