Refrigerant Circuit
1.3

RXTQ60TAVJU

No. in
piping
Symbol
diagram
(1)
M1C
Inverter compressor
M1F
(2)
Inverter fan
M2F
Electronic expansion valve
(3)
Y1E
(Main)
Electronic expansion valve
(4)
Y3E
(Subcooling)
(5)
Y1S
Four way valve
(6)
S1NPH High pressure sensor
(7)
S1NPL Low pressure sensor
(8)
S1PH
High pressure switch
(9)
Fusible plug
Pressure regulating valve 1
(10)
(Receiver to discharge pipe)
(11)
R1T
Thermistor (Outdoor air)
(12)
R2T
Thermistor (Discharge pipe)
(13)
R3T
Thermistor (Suction pipe 1)
Thermistor (Heat exchanger
(14)
R4T
deicer)
(15)
R5T
Thermistor (Suction pipe 2)
Thermistor (Subcooling heat
(16)
R6T
exchanger gas pipe)
(17)
R7T
Thermistor (Liquid pipe)
FIN
(18)
Thermistor (Radiation fin)
TH
11
Name
Inverter compressor is operated on frequencies between 36Hz and 195Hz by using the
inverter.
Because the system is of an air heat exchange type, the fan is operated at 8-step rotation
speed by using the inverter.
While in heating operation, PI control is applied to keep the outlet superheated degree of
air heat exchanger constant.
Pl control is applied to keep the outlet superheated degree of subcooling heat exchanger
constant.
Used to switch the operation mode between cooling and heating.
Used to detect high pressure.
Used to detect low pressure.
In order to prevent the increase of high pressure when an error occurs, this switch is
activated at high pressure of 4.0 MPa (580 psi) or more to stop the compressor operation.
In order to prevent the increase of pressure when abnormal heating is caused by fire or
others, the fusible part of the plug is molten at a temperature of 70 ~ 75°C (158 ~ 167°F) to
release the pressure into the atmosphere.
This valve opens at a pressure of 4.0 MPa (580 psi) or more for prevention of pressure
increase, thus resulting in no damage of functional parts due to the increase of pressure in
transportation or storage.
Used to detect outdoor air temperature, correct discharge pipe temperature, and others.
Used to detect discharge pipe temperature, make the temperature protection control of
compressor, and others.
Used to detect suction pipe temperature, keep the suction superheated degree constant in
heating operation, and others.
Used to detect liquid pipe temperature of air heat exchanger, determine defrost operation,
and others.
Used to the calculation of an internal temperature of compressor etc.
Used to detect gas pipe temperature on the evaporation side of subcooling heat
exchanger, keep the superheated degree at the subcooling heat exchanger constant, and
others.
Used to detect refrigerant overcharge in check operation, and others.
• Used for outdoor unit fan speed control.
• Used for inverter radiation fin temperature control.
• Used for pressure difference control.
Function
SiUS331604E
Refrigerant Circuit