6.3.2 With the Optional Infrared Floor Sensor
Whether the thermostat is turned on or off is determined by the difference between the remote controller set
temperature and the detected temperature around people.
Normal operation
· Cooling operation
· Heating operation
Dry operation
· When Tro
24.5°C (76.1°F)
· When Tro > 24.5°C (76.1°F)
∗: Description of symbols
T = Detected room temperature – Remote controller set temperature
Tro = Detected room temperature at the start of dry operation
Tr = Determined by the room temperature detected by the thermistor
Control range of temperature around people
When the floor temperature is very low, operation using the temperature around people may cause the suction
air temperature to operate outside of use range.
To avoid the above condition, a limit based on the suction air temperature is set for the use range of the
temperature around people.
Heating operation
· When the floor temperature is higher than suction air temperature (R1T), R1T will be treated as the control
target temperature in operation.
· When the temperature around people is 33°C (91.4°F) or higher, R1T will be treated as the control
temperature for operation.
Cooling operation
· When the floor temperature is lower than suction air temperature (R1T), R1T will be treated as the control
target temperature for operation.
· When the temperature around people is 15°C (59°F) or lower, R1T will be treated as the control temperature
for operation.
Functions and Control
∆T ≤ –1.0˚C (–1.8˚F)
Normal operation
(Thermostat ON)
∆T ≥ +1.0˚C (+1.8˚F)
∆T ≥ +1.0˚C (+1.8˚F)
Normal operation
(Thermostat ON)
∆T ≤ –1.0˚C (–1.8˚F)
Tr < Tro – 1.0˚C (– 1.8˚F)
Dry operation
Tr > Tro + 1.0˚C (+ 1.8˚F)
Tr < Tro – 1.5˚C (– 2.7˚F)
Dry operation
Tr > Tro + 0.5˚C (+ 0.9˚F)
Outline of Control (Indoor Unit)
Thermostat OFF
Thermostat OFF
Thermostat OFF
Thermostat OFF