Troubleshooting by Error Code
Troubleshooting
219
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Are any
connected centralized
YES
controllers removed or the
address changed?
NO
Does the
NO
power supply of all the
centralized controllers
connect?
YES
Are the
reset switches of
NO
all the centralized controllers
set to the normal
position?
YES
Is the
NO
connection wiring broken
or wrong?
YES
Does
the centralized
YES
controller or the schedule
timer connect?
NO
A
Go to the next page
Is any
error displayed on
YES
the centralized controller or
the schedule
timer?
NO
SiUS331604E
Concurrently reset the
power supply of all the
centralized controllers.
Connect the power
supply of the
centralized controller.
Set the reset switch to
the normal position.
Correct the wiring.
Refer to the troubleshooting
of the centralized controllers
or the schedule timers.
Service Diagnosis