Daikin VRV IV-S RXTQ-TAVJU Series Service Manual page 51

Table of Contents

Advertisement

SiUS331604E
3.1.2 Startup Control in Heating Operation
Electric symbol
Outdoor unit
RXTQ36
actuator
TAVJU
Compressor
M1C M1C M1C 0 Hz
Outdoor fan
M1F
Four way valve
Y1S
Main electronic
Y1E
expansion valve
Subcooling
electronic
expansion valve
Hot gas bypass
Y2S
valve
Ending conditions
Functions and Control
Thermostat ON
Pressure equalization control
RXTQ48
RXTQ60
prior to startup
TAVJU
TAVJU
From starting
M1F M1F,
Ta > 20°C (68°F): STEP 1
M2F
Ta ≤ 20°C (68°F): OFF
Y1S
Y1S Holds
Y1E
Y1E 0 pulse
Y3E 0 pulse
OFF
• Pc – Pe < 0.3 MPa
OR
(43.5 psi)
• A lapse of 1 to 5 min.
Startup control
STEP 1
Increases 2 steps every 20 seconds
from minimum frequency
Minimum frequency
until Pc – Pe > 0.39 MPa
(56.6 psi) is achieved
STEP 8
STEP 8
ON
ON
0 pulse
0 pulse
0 pulse
0 pulse
OFF
OFF
OR
A lapse of 10 sec.
Special Control
STEP 2
• A lapse of 130 sec.
• Pc > 2.70 MPa
(392 psi)
• Pc – Pe > 0.39 MPa
(56.6 psi)
38

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rxtq36tavjuRxtq48tavjuRxtq60tavjuVrv iv-s seriesVrv iv-s rxtq36tavjuVrv iv-s rxtq60tavju ... Show all