(25) External Static Pressure Settings (for FXMQ model)
Mode No.
13 (23)
The Second Code No. is set to 07 (an external static pressure of 100 Pa (0.40
∗1. FXMQ15/18/24/30/36/48PB cannot be set to 30 Pa (0.12
∗2. FXMQ07/09/12PB cannot be set to 110-200 Pa (0.44-0.80
∗3. FXMQ54PB cannot be set to 30 Pa (0.12
(26) Setting of Humidifier / Air Purifier Fan Tap (for FXTQ model)
Mode No.
14 (24)
(27) Residual Operation Time (for FXTQ model)
Mode No.
14 (24)
(28) Thermostat OFF Excess Humidity
Setting to "Humidification Setting" turns ON the humidifier if suction air temperature is 20ºC or more and turns
OFF the humidifier if suction air temperature is 18ºC or below when the heating thermostat is OFF.
Mode No.
15 (25)
(29) Direct Duct Connection
This is used when "fresh air intake kit equipped with fan" is connected. The indoor unit fan carries out residual
operation for 1 minute after the thermostat is stopped. (For the purpose of preventing dust on the air filter from
falling off.)
Mode No.
15 (25)
Field Setting
Second Code
First Code No.
No.
01
02
03
04
05
06
07
6
08
09
10
11
12
13
14
15
Second Code
First Code No.
No.
01
4
02
Second Code
First Code No.
No.
01
5
02
03
Second Code
First Code No.
No.
01
1
02
Second Code
First Code No.
No.
01
2
02
30 Pa (0.12 inWG) (∗1) (∗3)
110 Pa (0.44 inWG) (∗2)
120 Pa (0.48 inWG) (∗2)
130 Pa (0.52 inWG) (∗2)
140 Pa (0.56 inWG) (∗2)
150 Pa (0.60 inWG) (∗2) (∗3)
160 Pa (0.64 inWG) (∗2) (∗3)
180 Pa (0.72 inWG) (∗2) (∗3)
200 Pa (0.80 inWG) (∗2) (∗3)
inWG
).
).
inWG
) or 150-200 Pa (0.60-0.80
inWG
Remote controller setting
Field Setting from Remote Controller
Contents
50 Pa (0.20 inWG)
60 Pa (0.24 inWG)
70 Pa (0.28 inWG)
80 Pa (0.32 inWG)
90 Pa (0.36 inWG)
100 Pa (0.40 inWG)
inWG
)) at factory setting.
).
inWG
Contents
H tap
Contents
30 seconds
60 seconds
120 seconds
Contents
Not equipped
Equipped
Contents
Not equipped
Equipped