SiUS331604E
4.53 Address Duplication, Poor Setting
MC
Error Code
Applicable
Centralized controller
Models
intelligent touch controller
Schedule timer
Method of Error
DIII-NET communication data is used to detect the error.
Detection
Error Decision
Multiple centralized controllers or intelligent touch controllers are connected, and the controllers are
Conditions
both set as master centralized controllers or slave centralized controllers.
Two schedule timers are connected.
Supposed
Causes
Service Diagnosis
Centralized controller address duplication
Troubleshooting by Error Code
214