Standby Control
3. Standby Control
3.1
Restart Standby
Used to forcedly stop the compressor for a period of 3 minutes, in order to prevent the frequent ON/OFF of the
compressor and equalize the pressure within the refrigerant system.
In addition, the outdoor fan carry out the residual operation for a while to suppress the acceleration of the
pressure equalizing and melting of the refrigerant to the evaporator.
3.2
Crankcase Heater Control
In order to prevent the refrigerant from melting in the compressor oil in the stopped mode, this mode is used to
control the crankcase heater.
53
temperature < 70˚C (158 ˚F)
Crankcase heater
OFF
temperature > 75˚C (167 ˚F)
Discharge pipe
Discharge pipe
Crankcase heater
ON
Functions and Control