Daikin VRV IV-S RXTQ-TAVJU Series Service Manual page 98

Table of Contents

Advertisement

Field Setting from Remote Controller
2.3.1 Detailed Explanation of Setting Modes
(1) Filter Contamination Heavy/Light
If switching the filter sign ON time, set as given in the table below.
Mode No.
10 (20)
FXTQ
Mode No.
10 (20)
(2) Long Life Filter Type
When a Ultra long life filter is installed, the filter sign timer setting must be changed.
Mode No.
10 (20)
FXTQ
Mode No.
10 (20)
(3) (5) (10) Selecting of Thermistor
Select a thermistor to control the room temperature.
When the unit is not equipped with an infrared floor sensor:
Mode No.
10 (20)
The factory setting for the Second code No. is 01 and room temperature is controlled by the suction air thermistor
for indoor unit and
controlled by the suction air thermistor. When the Second code No. is set to 03, room temperature is controlled
by the
remote controller thermistor
85
Second Code
First Code No.
No.
01
0
02
Second Code
First Code No.
No.
01
0
02
Second Code
First Code No.
No.
01
1
02
Second Code
First Code No.
No.
01
1
02
Second Code
First Code No.
No.
01
2
02
03
remote controller thermistor
.
Standard Filter Long Life Filter Ultra Long Life
200 hrs.
2,500 hrs.
100 hrs.
1,250 hrs.
Remote controller thermistor and suction air thermistor for indoor
unit
Suction air thermistor for indoor unit
Remote controller thermistor
. When the Second code No. is set to 02, room temperature is
Filter
10,000 hrs.
5,000 hrs.
Contents
Light
Heavy
Contents
Long Life Filter
Ultra Long Life Filter
Contents
2,500/1,250
10,000/5,000
Contents
SiUS331604E
Contents
Contamination
Light
Contamination
Heavy
Field Setting