Mitsubishi Electric Melsec Q Series User Manual page 61

Ethernet interface module
Hide thumbs Also See for Melsec Q Series:
Table of Contents

Advertisement

2 USING THE E-MAIL FUNCTION
Item name
Condition for PLC
Select the monitoring condition for the
Inspection
CPU
Send Method
Select the data send method.
Set the data format for the attached
Attached File Form
file
Attached File Name
Set the attached file name
Set time interval between reading the
PLC Inquiry Interval
CPU status and device values and
the units (h/min/s)
Input Format of
Select the input format of the
Inspection Value
monitoring data
Condition Device
Set the condition device
Condition for Inspection
Set the monitoring condition
Monitoring Value
Set the monitoring value
News Data Storage
News data storage device value
Device
News Data Points
Set the news data points
2 - 33
Description of setting
1 When an e-mail is sent with the programmable controller status
inspection, only subject (programmable controller CPU status is stored)
is sent.
(1) Condition for PLC inspection
Condition for PLC inspection
Normal STOP
Serious/Fatal Error
Warning STOP
Normal RUN
Warning RUN
PAUSE
News settings
Notification condition
CPU status
monitoring ( 1)
monitoring
Sends an e-mail when the programmable controller CPU is placed in the
STOP status normally.
Sends an e-mail when an error that stops the CPU execution has occurred.
Sends an e-mail when the programmable controller CPU is stopped by an
external operation, etc. while an error that allows to continue the CPU
execution has occurred.
Sends an e-mail when the programmable controller CPU is placed in the
RUN status normally.
Sends an e-mail when an error that does not allow to continue the CPU
execution has occurred while the programmable controller CPU is in the
RUN status. (The programmable controller CPU is in operation.)
Sends an e-mail when the programmable controller CPU is placed in the
PAUSE status.
MELSEC-Q/L
Setting range/option
Device
• No Setting
• Normal STOP
• Serious/Fatal Error
• Warning STOP
(Moderate error STOP)
• Normal RUN
• Warning RUN
(Moderate Error STOP)
• PAUSE
• Send Attached File
• Send Text Mail
• Binary
• ASCII
• CSV
• Up to 8 characters
• 30 s to 24 h
• DEC
• HEX
• A device in the CPU module
• -32768 to 32767
[Maximum points for a device]
• Word device: 960 points
• Bit device: 8192 points
[Total number of points]
• Total number of news data points:
1920 bytes
(One bit point is rounded up to one
word point.)
: Setting item
: Setting not required
Description
2 - 33

Advertisement

Table of Contents
loading

Table of Contents