Mitsubishi Electric Melsec Q Series User Manual page 159

Ethernet interface module
Hide thumbs Also See for Melsec Q Series:
Table of Contents

Advertisement

5 WHEN USING FILE TRANSFER FUNCTIONS (FTP SERVER)
5 - 26
pwd
[Function]
[Designation format]
[Caution]
quit
[Function]
[Designation format]
[Same function]
quote
[Function]
[Designation format]
[Designation example]
[Caution]
rename
[Function]
[Designation format]
[Designation example]
[Caution]
user
[Function]
[Designation format]
[Designation example 1]
[Designation example 2]
[Caution]
Displays the current directory name of a CPU module.
pwd
• Each memory of a CPU module do not have any sub-
directories, and the files are stored in the root directory.
Therefore, "\" is displayed as the execution result of the pwd
command.
Disconnects the connection to the FTP server, and ends FTP.
quit
bye
Sends the FTP server subcommand (Ethernet module
dedicated command).
quote Ethernet module DEDICATED COMMAND
Ethernet module dedicated command: See (2).
quote status
• Only the Ethernet module dedicated command shown in
(2) can be designated directly after the quote command.
Changes the file name of a CPU module.
rename FILE PATH BEFORE CHANGE FILE PATH
AFTER CHANGE (abbreviated as ren)
To change the file name of the file stored in the RAM of
memory card:
rename 1:\MAINSEQ1.QPG 1:\SEQ1OLD.QPG
• Upon normal completion, either of the following response
codes is shown.
350 Need more info.
250 Rename successful
• See sections 5.5 and 5.6.1.
Enter the user name and password for the connected FTP
server.
User
: User name [Password]
User name: FTP login name set during Ethernet module "FTP
parameter setting"
Password : Password set during Ethernet module "FTP
parameter setting"
(See Sections 5.3 for the FTP login name and
password.)
To designate the user name:
user QJ71E71
To designate both user name and password:
user QJ71E71 QJ71E71
• The password entry from the keyboard is not displayed.
MELSEC-Q/L
5 - 26

Advertisement

Table of Contents
loading