5 WHEN USING FILE TRANSFER FUNCTIONS (FTP SERVER)
5 - 30
cpuchg (Q series Ethernet module's dedicated command)
[Function]
[Designation format]
Command
quote cpuchg
quote cpuchg controlPLC
quote cpuchg no1
quote cpuchg no2
quote cpuchg no3
quote cpuchg no4
[Designation example 1]
[Designation example 2]
[Caution]
This command designates an access target CPU with a
multiple CPU system configuration. Alternatively, it displays
the current access target CPU.
quote cpuchg [access target CPU]
Access target CPU: Designate the CPU to which file access is
to be performed.
Description
Checks the current access target CPU.
Designates the control CPU as the access target CPU.
Designates the CPU No. 1 as the access target CPU.
Designates the CPU No. 2 as the access target CPU.
Designates the CPU No. 3 as the access target CPU.
Designates the CPU No. 4 as the access target CPU.
• When the command is successfully completed, the
execution result is displayed as follows:
When setting the access target CPU:
200 Command Okey
When displaying the access target CPU:
200 Target cpu is "access target CPU"
• If the designated access target CPU does not exist, the
following message is displayed.
557 Cpu not found
When designating the access target CPU as the control CPU
quote cpuchg controlPLC
When displaying the currently selected access target CPU
quote cpuchg
The control CPU of the Ethernet module will be the access
target CPU after logging in when the OPEN/USER command
is executed to the Ethernet module.
MELSEC-Q/L
5 - 30