Manual
The individual function blocks are described below.
1.5.2.1 Arithmetic Ar1 to Ar6
Ar1 to Ar6
Ar .F
E1
ncon
Ar .1
E2
ncon
Ar .2
E1 · E2+E3-E4
E3
0.000
Ar .3
E5
0.000
Ar .4
E4
1.000
Ar .5
E5
Figure 1-7
Function block Arithmetic Ar1 to Ar6
-- With this function block the four basic arithmetic functions are implemented with appropriate
assignment of inputs 0 and 1 respectively. The preset E3=E4=0, E5=1 gives A = E1×E2.
-- Typical process-technical applications are dosing or evaluation (E1×E2), range fade-outs
(E1×E2+E3) or differentiations (E3 - E4).
1.5.2.2 Function transmitter Fu1 and Fu2
Fu1, Fu2
Fu .F
A
E
ncon
Fu .1
-10, 0, 10 bis 90, 100, 110oFPA
Figure 1-8
Function block function transmitter
The function transmitter assigns every value of the input variable E in the range from -10 % to
+110 % an output variable A in the range from -199,9 % to +199,9 % with the function entered
by the user: A = f(E). The function is entered by the parameters "vertex value 1 to 13" for -10 %
to +110 % of E in intervals of 10 %. Parabolae are set by the computing program between
these vertex values which interlink tangentially the vertex values so that a constant function is
produced. The vertex values at -10 % and +110 % of E are required for the overflow. The last
rise remains constant in the case of further overmodulation of E. When used as a linearizer for
the displays, the linearization function is entered by the 13 vertex values so that the series
circuiting of the sensor function gives a linear equation with the linearization function
(see chapter 1.5.4, figure 1-20 to figure 1-23, page 46).
1.5.2.3 Maximum value selection MA1 to MA3
MA1.F to MA3.F
MA .F
E1
MA .1
ncon
E2
Max
ncon
MA .2
E3
0.050
MA .3
Figure 1-9
Function block maximum value selection
With the preset the greater value of E1 or E2 is connected through to A and at the same time
limited to the value of E3 (-5 %). Typical applications are maximum value selection circuits and
minimum value limitings.
SIPART DR22 6DR2210
C79000-G7476-C154-03
1.5.2
nr
E1 · E2 + E3 - E4
A =
A
Ar
.6
E5 is limited to values ≥0.5 %.
nr
A
Fu
.2
A = f(E)
E
nr
A = max (E1,E2, E3)
The greatest of the three input values is
A
MA .4
connected through to the output.
1.5 Functional description of the structure switches
Analog input signal processing freely connected (S4 = 1)
E5
1 Technical Description
27