0 to 100%. At the same time, tS presets the floating time for 0 to 100% change in incremen-
tal setpoint adjustment via the control signals
to 1.
With the setpoint ramp, setpoint switchings can be effected to non-followed-up variables SH
and wi, w
, w
at S52 = 1 and w
EΔ
ES
not suddenly but with the set ramp.
w
w
E
Δw
μ
S
H
tw
safe
external
Setpoint
Setpoint
Figure 1-18
Setpoint switching with ramp
With the control signals tS and tSII the set setpoint ramps can be switched off.
-- Setpoint limits SA, SE
(accordingly SAII, SEII at S1 = 12)
With the parameters SA and SE (oFPA) the effective setpoint w can be limited to minimum
value (SA) and maximum value (SE) in the range from -10 to 110 %.
Exception: Ratio controller (S1 = 4) and ratio cascade, commanded ratio controller (S1 = 6)
-- Follow-up of the ineffective setpoint to the active setpoint (S52)
(accordingly S235 at S1 = 12)
Normally the ineffective setpoint is followed up to the effective setpoint so that the setpoint
switching is bumpless. The internal setpoint (wi), the external setpoint incrementally
adjustable via Δw (w
The safety setpoint SH cannot be followed up. The external setpoint w
inputs can only be followed up indirectly by following up the supplying device on the output
side. To do this the effective w is used as a follow-up variable, assigned to an analog output
and as a follow--up control signal the OR-operation H∨N∨Si, assigned to a digital output.
At S52 = 1 the follow-up is suppressed. This switch setting is always required especially in
follow-up controllers if the internal setpoint represents a kind of safety function or if multiple
setpoint operation is to be run in follow-up controller (S1 = 3).
-- x-tracking (S50)
(accordingly S233 at S1 = 12)
With the structure switch S50 = 1, x-tracking (ratio controller xv-tracking) can be switched
on. This means that the setpoint is followed up to the actual value or the nominal ratio is
followed up to the actual ratio and therefore a control difference xd is reset to 0. The follow
up always takes place when there is no automatic operation (A). This is the case in manual
mode (H), follow-up mode (N), DDC mode and in operation with safety manipulated variable
(Si): A = H∨N∨Si
SIPART DR22 6DR2210
C79000-G7476-C154-03
if the supplying controller has not been followed up
EA ,
tan α = 100 %
tS
Δw · tS
t
=
w
100 %
t
) and the external setpoint via the SES (w
EΔ
1.5 Functional description of the structure switches
1.5.4 Controller types (S1, S49 to S53)
Δw. At tS = oFF the adjustment speed goes
=
Δw
tw
ES
1 Technical Description
) can be followed up.
via the analog
EA
41