Siemens SIPART DR22 Manual page 225

Hide thumbs Also See for SIPART DR22:
Table of Contents

Advertisement

Manual
Process operation
level; see
chapter 3.1, pg. 167
if nec. controller
see
selection
fig.
controller I
3-3,
or controller II,
page
Switch controller
170
to manual
operation, set the
desired operating
point and wait for
stationary
condition!
Filters tFI, tFII
and tF1 to tFb
and floating time
tY must be set!
At S-controller
tA, tE and tY
must be set!
Switch controller
to automatic
Exit
mode, old
key
parameters **.o
(2)
are active
Switch controller
to automatic
Exit
operation, new
key
parameters **.n
(2)
are active
Figure 4-1
Parameterization mode AdAP
*
loop order 1 to 8
** Parameter name
1)
Enter function only active in manual operation (in the case of adaptation of the master controller in cascades (S1 = 5/6)
master controller set to Internal and Automatic)
2)
Error message
no AUto
If new parameters are selected and there is parameter control, the flashing error message no AUto appears after pressing
the Exit key (no automatic transfer).
Press the Enter key:
Pressing the Exit key:
SIPART DR22 6DR2210
C79000-G7476-C154-03
Selection level
AdAP
Enter
key
Adaptation
(9)
after process
operation
1)
Repeat
adaptation
Exit
key
(2)
Old
Exit
parameters
key
**.o are
(2)
retained
Exit
key
(2)
Exit
key
(2)
Old parameters
**.o are
overwritten by
Exit
new
key
parameters **.n
(2)
2)
Error is acknowledged; return to parameterization mode AdAP; the parameters gained from
the adaptation can be noted.
Jump to the parameterization preselection mode AdAP; the new parameters **.n are
deleted. On jumping to the parameterization mode AdAP, Strt AdAP appears in **.n.
4.5 Automatic setting of control parameters
Parameterization mode AdAP
Pre-adaptation ↗ Presettings
Adaptation LED (4) OFF
tU
oFF,0.1 to 24 h
Monitoring time
Direction
dPv nEG, PoS
Amplitude
dY 0.5 to 90 %
Start adaptation
**.o Pi or Pid
**.n Strt AdAP
During adaptation
Adaptation LED (4) flashing
Complete process display
Enter
Aborted adaptation
key (9)
Adaptation LED (4) OFF
by error
messages
of the adap-
Error
tation
message
procedure
display
see table 3-2, pg. 177
Post adaptation
Adaptation LED (4) ON
cP.o
Pi or Pid
AH.o
Keys (13)
±∆y
2)
cP.n
Pi.*
cP.n
Pid.*
AH.n
4 Commissioning
of the step
command
Enter key (9)
manual
via
Exit key
old
parameters
new
parameters
223