Application examples for configuring the controller

Example 1
Block diagram control circuit
wi
x
Structure switch Strs
Switch
Value
S
5
2
AE1: 4 to 20 mA
S
69
1
AA1: 4 to 20 mA
Parameter oFPA
Para-
Value
meters
*)
dP1
Decimal point
dA1
*)
Display start value
*)
dE1
Display full scale value
Parameter onPA
Para-
Value
meter
*)
cP1
Proportional action
factor
tn1
*)
Integral action time
*) Setting as required
Attention:
-- All settings starting from the factory setting (APSt) of the controller
-- The above settings/adaptations are absolutely essential.
Other parameters (e.g. A1 / A2 / ... ) as required.
SIPART DR22 6DR2210
C79000-G7476-C154-03
Fixed setpoint controller with K-output
controlled variable via four--wire transmitter
The controlled variable x from a four--wire transmitter goes to
the analog input AE1, signal range 4 to 20 mA.
The manipulated variable y with 4 to 20 mA goes through AA1
to a position controller SIPART PS.
Meaning
Meaning
AE3
Meaning
7 Application examples for configuring the controller
SIPART-DR22 Standard controller
AE2
AE1
AA
--
--
--
3 2 1
+
--
I
U
H
PE
UC 24 C
N
L
PE
AC 115 V
N
AC 230 V
L
BA
M
L
8 7 6 5
--
SIPART
PS
+
235