3 Operation
3.3 Configuring level (parameterization and structuring mode)
3.3.3 Parameterization mode AdAP (Adaptation)
Process operation
level, see chapt. 3.1,
pg. 167
if nec. controller
see
selection
fig.
controller I
3-3,
or controller II,
page
Switch controller
170
to manual mode,
set the desired
operating point
and wait for
stationary
condition!
Filters tFI, tFII
and tF1 to tFb
and floating time
tY must be set!
In the S-controller
tA, tE and tY
must be set!
Switch controller
to automatic
Exit
operation, old
key
parameters **.o
(2)
are active
Switch controller
to automatic
Exit
operation, new
key
parameters **.n
(2)
are active
Figure 3-5
Parameterization mode AdAP
*
loop order 1 to 8
**
parameter name
1)
Enter function only active in manual operation (in the case of adaptation of the master controller in cascades (S1 = 5/6) master controller
set to Internal and Automatic)
2)
Error message
no AUto
If new parameters are selected and there is parameter control, the flashing error message no AUto appears after pressing the Exit
key (no automatic transfer).
Press the Enter key:
Error is acknowledged; return to parameterization mode AdAP; the parameters won by adaptation
can be noted.
Pressing the Exit key: Jump to the parameterization preselection mode AdAP; the new parameters **.n are deleted.
On jumping to the parameterization mode AdAP, Strt AdAP appears in **.n.
178
Selection level
AdAP
Enter
key
Adaptation
(9)
after process
operation
1)
Repeat
adaptation
Exit
key
(2)
Old
Exit
parameters
key
**.o are
(2)
retained
Exit
key
(2)
Exit
key
(2)
Old parameters
**.o are
overwritten by
Exit
new parameters
key
**.n
(2)
2)
Parameterization mode AdAP
Pre-adaptation ↗ Presettings
Adaptation LED (4) OFF
tU
oFF,0.1 to 24 h
Monitoring time
Direction
dPv nEG, PoS
Amplitude
dY 0.5 to 90 %
Start of adaptation
**.o Pi or Pid
**.n Strt AdAP
During adaptation
Adaptation LED (4) flashing
Complete process display
Enter
aborted adaptation
key (9)
Adaptation LED (4) OFF
by
error mes-
sages
Error
of the adap-
message
tation
display
procedure
see table 3-2, pg. 177
Post adaptation
Adaptation LED (4) ON
cP .o
Pi or Pid
AH.o
±∆y
Keys (139
2)
cP .n
Pi.*
cP .n
Pid.*
AH.n
Manual
of the step
trigger
Enter key (9)
manual
via
Exit key
old
parameters
new
parameters
SIPART DR22 6DR2210