Manual
Digital display
y
x
w
Adjustment/
Adjustment/
display area
vvc
0.100 -- 10.00
cP1
cP3
cP5
0.1 -- 100
cP7
cP9
tn1
tn3
tn5
1 -- 9984
tn7
tn9
tv1
tv3
tv5
oFF, 1 -- 2992
tv7
tv9
AH1
AH3
AH5
0.0 -- 10.0
AH7
AH9
Y01
Y03
Y05
Auto, 0.0 -- 100.0
Y07
Y09
SG means: controlling variable for the parameter control
Table 3-7
Parameter list PASt
Error messages
-
tv Err:
If tv.1 to tv.9 have not been set all = off or have not been set all ≠ off, the error message tv Err
appears when returning to the structuring preselection mode after PASt with the Exit key.
Pressing the Enter key:
Error correction possibility by jumping to tv.1 in the structuring mode PASt.
Pressing the Exit key:
Error message is acknowledged, return to the structuring preselection level after PASt, tv.1 to
tv.5 are automatically set to oFF.
-
Y0 Err:
If Y0.1 to Y0.9 have not been set all = AUto or have not been set all ≠ AUto, the error message
Y0 Err appears on returning to the structuring preselection level after PASt with the Exit key.
Pressing the Enter key:
Error correction possibility by jumping to the structuring mode PASt after Y0.1.
Pressing the Exit key:
Error message is acknowledged, return to the strucuring preselection level after PASt, Y0.1 to
Y0.2 are automatically set to AUto.
SIPART DR22 6DR2210
C79000-G7476-C154-03
3.3
Configuring level (parameterization and structuring mode)
Factory
Resolution
setting
setting
5
128 values/
octave
0.1
128 values/
octave
0.1
0.1
0.1
0.1
9,984
128 values/
octave
9,984
9,984
9,984
9,984
oFF
128 values/
octave
oFF
oFF
oFF
oFF
0.0
0.0
0.1
0.0
0.0
0.0
0.0
0.0
0.1
0.0
0.0
0.0
3.3.5
Structuring mode PASt (parameter control)
Dimen-
Parameter meaning
sion
sion
1
Derivative action gain
1
Proportional action factor at SG = 10 %
1
Proportional action factor at SG = 30 %
1
Proportional action factor at SG = 50 %
1
Proportional action factor at SG = 70 %
1
Proportional action factor at SG = 90 %
s
Integral action time at SG = 10 %
s
Integral action time at SG = 30 %
s
Integral action time at SG = 50 %
s
Integral action time at SG = 70 %
s
Integral action time at SG = 90 %
s
Derivative action time at SG = 10 %
s
Derivative action time at SG = 30 %
s
Derivative action time at SG = 50 %
s
Derivative action time at SG = 70 %
s
Derivative action time at SG = 90 %
%
Response threshold at SG = 10 %
%
Response threshold at SG = 30 %
%
Response threshold at SG = 50 %
%
Response threshold at SG = 70 %
%
Response threshold at SG = 90 %
%
Operating point P-Reg. at SG = 10 %
%
Operating point P-Reg. at SG = 30 %
%
Operating point P-Reg. at SG = 50 %
%
Operating point P-Reg. at SG = 70 %
%
Operating point P-Reg. at SG = 90 %
3 Operation