Measuring Range For Mv (Sens=Mv.); Measuring Range For U, I (Sens=Mv.) - Siemens SIPART DR22 Manual

Hide thumbs Also See for SIPART DR22:
Table of Contents

Advertisement

3 Operation
3.3 Configuring level (parameterization and structuring mode)
3.3.12 Set structuring mode CAE4/CAE5 -- UNI module(s)
The corresponding settings of the CAE4(5) menus for the different signal transmitters are
described below.
The range and thus the current measured value can be corrected with the parameters CA/CE to
compensate tolerances of the transmitters or adjustments with other display instruments.

3.3.12.1 Measuring range for mV (SEnS=Mv.)

D MA/ME measuring range
Call parameters MA, ME, set range start and full scale:
--175 mV ≤ MA ≤ ME +175 _C
D CA/CE fine adjustment
Call parameter CA:
Set signal at the low end of the range, correct the display with CA if necessary.
Call parameter CE:
Set signal at the top end of the range, correct the display with CE if necessary.

3.3.12.2 Measuring range for U, I (SEnS=Mv.)

D MA/ME measuring range
The setting is made in mV (--175 mV to +175 mV);
The input signal types U and I are set to range 0/20 to 100 mV in the measuring range plug
(6DR2805--8J);
Example:
0 to 10 V or 0 to 20 mA:
2 to 10 V or 4 to 20 mA:
Call parameters MA, ME, set range start and full scale.
D CA/CE fine adjustment
Call parameter CA:
Set signal at the low end of the range, correct the display with CA if necessary.
Call parameter CE:
Set signal at the top end of the range, correct the display with CE if necessary.
212
MA = 0,
ME = 100;
MA = 20,
ME = 100
Manual
SIPART DR22 6DR2210
C79000-G7476-C154-03