Table 5-5 Representation Of Analog Values In The ±1 V To ±10 V Voltage Measuring Range - Siemens SIMATIC S7-300 Manual

Automation system, module data
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Representation of the analog values of analog modules
5.1 Representation of the analog values of analog input channels
Representation of analog values in voltage measuring ranges
Table 5-5
Representation of analog values in the ±1 V to ±10 V voltage measuring range
System
Voltage measuring range
dec
hex
±10 V
32767
7FFF
11.851 V
32512
7F00
32511
7EFF
11.759 V
27649
6C01
27648
6C00
10 V
20736
5100
7.5 V
1
1
361.7 µV
0
0
0 V
-1
FFFF
-20736
AF00
-7.5 V
-27648
9400
-10 V
-27649
93FF
-32512
8100
-11.759 V
-32513
80FF
-32768
8000
-11.851 V
Table 5-6
Representation of analog values in the ±80 mV to ±500 mV voltage measuring ranges
System
Voltage measuring range
dec
hex
±500 mV
32767
7FFF
592.6 mV
32512
7F00
32511
7EFF
587.9 mV
27649
6C01
27648
6C00
500 mV
20736
5100
375 mV
1
1
18.08 µV
0
0
0 mV
-1
FFFF
-20736
AF00
-375 mV
-27648
9400
-500 mV
-27649
93FF
-32512
8100
-587.9 mV
-32513
80FF
-32768
8000
-592.6 mV
5-4
±5 V
±2.5 V
5.926 V
2.963 V
5.879 V
2.940 V
5 V
2.5 V
3.75 V
1.875 V
180.8 µV
90.4 µV
0 V
0 V
-3.75 V
-1.875 V
-5 V
-2.5 V
-5.879 V
-2.940 V
-5.926 V
-2.963 V
±250 mV
±80 mV
296.3 mV
94.8 mV
294.0 mV
94.1 mV
250 mV
80 mV
187.5 mV
60 mV
9.04 µV
2.89 µV
0 mV
0 mV
-187.5 mV
-60 mV
-250 mV
-80 mV
-294.0 mV
-94.1 mV
-296.3 mV
-94.8 mV
±1 V
1.185 V
Overflow
1.176 V
Overshoot range
1 V
0.75 V
36.17 µV
Nominal range
0 V
-0.75 V
-1 V
Undershoot range
-1.176 V
Underflow
-1.185 V
Overflow
Overshoot range
Nominal range
Undershoot range
Underflow
S7-300 Automation System Module data