Messages and diagnostics
8.5 Faults and remedial actions on the 3RW5 HMI High Feature
8.5
Faults and remedial actions on the 3RW5 HMI High Feature
Faults
HMIFault
FWUpdateUnsuccessful
FWUpdateInvalidSignature
Error during self-test
LIDefective
Local interface disabled due to
flooding
Write Error
ReadError
File system error
No device answer
138
Cause
Unrecoverable error detected after
internal diagnostics (self-test, etc.).
The firmware is incomplete and/or
the firmware expansions are
incomplete or incompatible.
Unrecoverable error detected after
internal diagnostics (self-test, etc.).
Too many requests to the local
device interface
File cannot be written to the micro
SD card.
File cannot be read from the micro
SD card.
Micro SD card cannot be read.
The connection to the connected
basic unit has been interrupted.
Remedy
Replace the device.
Run a complete firmware update.
•
Check any occurring error messages.
•
Check to see whether or not the firmware
•
update was aborted.
Replace the device.
The interface remains disabled until it is no
longer flooded with requests.
Check whether the micro SD card is
•
inserted.
Check whether the micro SD card is
•
write-protected.
Check whether the micro SD card is
•
inserted.
Create and copy a new file onto the micro
•
SD card.
Format the micro SD card using FAT32 file
format.
Check the connection between the HMI and
the device.
SIRIUS 3RW52 Soft Starter
Manual, 01/2019, A5E35630451002A/RS-AD/004