Siemens SIRIUS 3RW52 Manual page 137

Industrial controls, soft starters and solid-state switching devices
Hide thumbs Also See for SIRIUS 3RW52:
Table of Contents

Advertisement

Error
Fault
No.
1)
1466
Contact 1 failed
1467
Contact 2 failed
1468
Contact 3 failed
1479
Phase angle
control failure
1482
Current
measuring range
overshot
1523
Device error
1755
Overtemperature
of electronic
components
Visible on the display of the 3RW5 HMI Standard.
1)
Acknowledgment depends on parameter RESET MODE.
2)
SIRIUS 3RW52 Soft Starter
Manual, 01/2019, A5E35630451002A/RS-AD/004
Cause
Remedy
Switching element
defective
Error occurs
without motor
starting:
Motor terminals
are incorrectly
connected.
Error in
configuration of
inside-delta
circuit.
There is a
ground fault.
Fault occurs during
starting:
Chosen starting
voltage too
high
With sensors: The
measured value
has exceeded the
range limits.
With actuators:
The output value
has exceeded an
upper limit value.
Irrecoverable fault
detected following self-
diagnostics (self-test,
contactor contacts,
switching element,
etc.).
The temperature in the
Check the ambient
components has
temperature or the
exceeded the
control cabinet cooling.
maximum limit.
8.4 Faults and remedial actions of the 3RW52 soft starter
Manual
RESET
-
Check the switching
elements for L1, L2,
and L3 and replace
any that are
defective.
Please contact
Technical Support
(Support Request
(Page 31)).
x
Check and correct
the wiring.
Adapt parameters.
x
Check the
interaction between
the module and the
sensor or actuator.
-
Replace the device.
Please contact
Technical Support
(Support Request
(Page 31)).
Messages and diagnostics
Remote
Auto RESET
RESET
-
-
x
-
x
-
-
-
137