Messages and diagnostics
8.4 Faults and remedial actions of the 3RW52 soft starter
Error
Fault
No.
1)
381
Device error
1408
Zero current after
ON command
1409
Phase failure L1
1410
Phase failure L2
1411
Phase failure L3
1417
Bypass defective
1418
Bypass protective
trip
1454
Incorrect module
slot or faulty
configuration
136
Cause
Remedy
Irrecoverable fault
detected following self-
diagnostics (self-test,
contactor contacts,
switching element,
etc.).
No current flow is
detected in the motor
feeder after an ON
command. Possible
causes:
Main circuit is
interrupted (fuse,
motor starter
protector)
Motor contactor or
contactor control is
defective
No load
The main energy
monitoring system has
detected a phase
failure.
Bypass defective
The error can also
be generated by
successive, brief
interruptions of the
control supply
voltage.
An excessively high
current has occurred
in bypass mode.
There is a difference
between a real slot
and a slot configured
in the
SIRIUS Soft Starter
ES (TIA Portal).
Manual
RESET
-
Replace the device.
Please contact
Technical Support
(Support Request
(Page 31)).
x
Acknowledgment
once the cause has
been rectified.
x
Acknowledgment
once the cause has
been rectified.
-
Check the bypasses
for L1, L2 and L3
and replace any that
are defective.
Please contact
Technical Support
(Support Request
(Page 31)).
x
Check the motor.
Check the
dimensioning of the
soft starter.
Acknowledgment
after cooling down
-
Ensure consistency
between plugged
and configured
module. A wiring
error may also exist
at the referenced
module.
After the cause is
eliminated, the error
self-acknowledges.
Manual, 01/2019, A5E35630451002A/RS-AD/004
Remote
Auto RESET
RESET
-
-
x
-
x
-
-
-
x
-
-
-
SIRIUS 3RW52 Soft Starter