Overview Of Parameters - Siemens SIRIUS 3RW52 Manual

Industrial controls, soft starters and solid-state switching devices
Hide thumbs Also See for SIRIUS 3RW52:
Table of Contents

Advertisement

Parameter assignment

5.2 Overview of parameters

5.2
Overview of parameters
Parameters
Trip class for motor
overload protection
Rated operational current I
of the motor
Current limiting value as a
multiple of the set rated
operational current I
motor
Ramp-up time
Starting voltage
Ramp-down time
Soft Torque
RESET MODE
The rated operational current I
1)
the rating plate specification of the manufacturer.
For meaning of scale, refer to laser-cut table on front panel of device.
2)
80
Symbol
e
1)
of the
e
of the motor may, according to the standard, deviate by 20% from
e
Setting range
10A, 10E, 20E, OFF
1 ... 16
2)
1.3 ... 7 x I
e
Max.
0 ... 20 s
If parameter value "0" is set, the
motor is switched on with a
ramp-up time of approx. 100 ms.
30 ... 100 %
0 ... 20 s
Off (LED off)
On (LED on)
Manual RESET (LED off)
Remote RESET (LED flashes
green)
Auto RESET (LED lit green)
Manual, 01/2019, A5E35630451002A/RS-AD/004
Factory setting
10A
16
4 x I
e
10 s
30 %
0 s
Off
Manual
RESET
SIRIUS 3RW52 Soft Starter