Mounting and dismantling
3.4 Installing / mounting / removing 3RW5 HMI
3.4.5

Installing the Standard 3RW5 HMI into the control cabinet door

Requirements
● Note the mounting positions, minimum clearances and ambient conditions stated on the
data sheet.
● 3RW5 HMI Standard (accessories)
● An HMI connecting cable (accessory) of suitable length
● Cutout of suitable size in the control cabinet door
● PZ2 screwdriver in installation with door mounting kit IP65
● Device depth of the Standard 3RW5 HMI:
– Total depth: 32 mm
– Embedded depth: 29 mm
● Permissible wall thickness of the cabinet door:
– Without IP65 door mounting kit: 1.5 to 3.0 mm
– With IP65 door mounting kit: 1.0 to 7.0 mm
● Optional accessories:
– IP65 door mounting kit
Procedure without door mounting kit IP65
Place the 3RW5 HMI Standard in the cutout of the control cabinet door
3RW5 HMI Standard engages audibly in the 4 fixtures
46
. Ensure that the
.
SIRIUS 3RW52 Soft Starter
Manual, 01/2019, A5E35630451002A/RS-AD/004