SI-05C.BOOK Page 72 Monday, November 6, 2000 4:13 PM
Test Operation
1.7

Low Noise / Demand Operation

External control adaptor for outdoor unit is required for each low noise and demand control zone.
72
By using a separate External control adaptor for outdoor unit and setting the outdoor unit address
(setting mode 2) for each low noise and demand control zone, demand and low noise operation is
carried out in accordance with contact input received from the adaptor in each zone.
¡
GGGGGG
Demand address
F1 / F2
F1 / F2
F1 / F2
(F1 / F2)
External control
adaptor for
outdoor unit
DS2·DS1
No. 0
Outdoor unit address setting (Setting mode 2; see page 59.)
External control adaptor for outdoor unit address setting
Decide and set demand address 0 - 31 for each demand and low noise control zone. (See fig. below.)
Set SS1 to "BOTH" (factory set) or "C / H."
¡
¡
GGGGG
Demand address
F1 / F2
F1 / F2
F1 / F2
F1 / F2
(F1 / F2)
External control
adaptor for
outdoor unit
DS2·DS1
No. 1
: http://splitoff.ru/tehn-doc.html
Test Operation Inverter K Series
SiE-05C
¡
¡
GGGG
G
Demand address
F1 / F2
F1 / F2
F1 / F2
(F1 / F2)
External control
adaptor for
outdoor unit
DS2·DS1
No. 2
(VL030)