Failure Diagnosis For Inverter System - Daikin VRV Inverter K Series Manual

Table of Contents

Advertisement

SI-05C.BOOK Page 159 Monday, November 6, 2000 4:13 PM
SiE-05C

4. Failure Diagnosis for Inverter System

4.1
Points of Diagnosis
The main causes for each malfunction code are given in the table below. (For details refer to the next page
and those following.)
— : Failure is impossible
Malfunction
Troubleshooting Inverter K Series
: Failure is probable
: Failure is possible
: Failure is improbable
Contents of
Inverter
code
malfunction
PC board
Other
power unit
L4
Radiator fin
temperature
rise
L5
Instantaneous
over-current
L8
Electronic
thermostat
L9
Stall
prevention
LC
Malfunction of
transmission
between
inverter PC
board and
outdoor unit
PC board
U2
Abnormal
current/
voltage
P1
Over-ripple
protection
P4
Defect of
radiator fin
temperature
sensor
Failure Diagnosis for Inverter System
Location of failure
Compressor
Refrigerant
Outdoor
Other
system
unit PC
board
: http://splitoff.ru/tehn-doc.html
Field
Point of diagnosis
cause
Is the intake port of
the radiator fin
clogged?
Inspect the
compressor.
Inspection the
compressor and
refrigerant system.
Inspection the
compressor and
refrigerant system.
Inspect the
connection
between the
inverter PC board
and outdoor unit PC
board. Next, inspect
the inverter PC
board.
• Inspect the fuse
on the inverter PC
board.
• Check the DC
voltage.
• Open phase
• Current/voltage
imbalance
• Defect of main
circuit wiring
Inspect the radiator
fin thermistor.
159