Test Operation
Remote Control
Forced OFF or ON/OFF control of indoor units can be input from outside.
Enables indoor units to be turned on and off by a building control or key control system.
1. Wiring method and specifications
Remote control is carried out by connecting input from outside to pins T1 and T2 on the terminal block (for
remote controller and transmission wiring)
Wiring specifications
Wiring thickness
Wiring length
Outside contact specs.
Forced OFF
Forced OFF by input A "ON" (remote controller prohibited)
Remote controller permitted by input A "OFF"
2. Operation contents
Input A of forced stop and stop operation operates as described in the table on the right.
3. Forced OFF and ON/OFF control selection
82
Sheathed vinyl cord or cable (double core)
0.75~1.25mm²
MAX 100m
Contact which guarantees min. applicable load of 15 VDC, 10 mA
Switch input by remote controller after turning on the power supply.
Set field setting mode with the remote controller.
When you enter the field setting mode, select mode No. 12, and set the first code No. to "1." for forced
OFF, set the second code No. to "01," and from ON/OFF control, set to "02." (Factory set is forced
OFF.)
ON/OFF control
On by input A "OFF" → "ON"
OFF by input A "ON" → "OFF"