Wiring Adaptor
Display Signal
Normal operation output terminals (W1, W2) and malfunction output terminals (W3, W4) are no voltage,
Fetch
constant contact output.
(Allowable current is 10 mA~3 A per contact.)
Output for each system is as given in the table below.
System
Individual control
or individual
display Group
control
Temperature
For wiring specifications, we recommend a min. 1.25 mm2 sheathed vinyl cord, length within 70 m.
Setting Input
The relationship of preset temperature and resistance is as given in the table below.
Preset
temperature
(˚C)
Resistance
(Ω)
Note:
Resistance given in the table includes resistance of the wiring.
5.2.3

Applicable Models and Whether Mounting Box is Required or Not

Model name Adaptor
FXYC-K
FXYK-K
FXYS-K
FXYM-Ka
FXYL(M)-K
FXYA-K
FXYH-K
FXYF-K
376
Output Both RY1 and RY2 OFF
OFF
All normal operation
16
17
18
19
20
21
22
0
5
13.8
22.4
31
39.4
48.2
~
~
~
~
~
~
~
3.4
11.6
20
28.4
36.4
44.8
52.8
Mounting box / plate
KRP4A51
Not required
KRP4A52
KRP1B93
KRP4A53
KRP1A90
: http://splitoff.ru/tehn-doc.html
Only RY1 ON
Only RY2 ON
Even one unit stopped due to
malfunction or transmission
malfunction between adaptor PC
board and indoor unit
23
24
25
26
27
28
29
56.6
65.2
73.8
82.4
91
99.4
108.6
~
~
~
~
~
~
~
61.2
69.4
77.8
85.8
94
102.2
110.4
Mounting position
Mounted inside electrical parts box
of main unit
Mounted outside main unit
Mounted outside main unit
Appendix Inverter K Series / PLUS Series
SiE-05C
30
31
32
117.2
125.8
134.2
~
~
~
119.2