Daikin VRV Inverter K Series Manual page 387

Table of Contents

Advertisement

SI-05C.BOOK Page 373 Monday, November 6, 2000 4:13 PM
SiE-05C
Temperature
For wiring specifications, we recommend a min. 1.25 mm² sheathed vinyl cord, length within 70 m.
Setting Input
The relationship of preset temperature and resistance is as given in the table below.
Preset
temperature
(˚C)
Resistance
(Ω)
Note:
Resistance given in the table includes resistance of the wiring.
5.1.4
Wiring Adaptor PC Board for Electrical Appendices Optional Accessories and Mounting
Position
(See adaptor for wiring for details on mounting position.)
Model name
Adaptor PC board optional accessories name
Adaptor PC board mounting box optional
accessories name
Adaptor PC board and mounting box storage
position
Note:
The mounting position of mounting boxes FXYF~H is inside the unit if using one adaptor PC board. If
equipped with an air cleaner unit, however, the mounting box is mounted on the side of the main body. If
using two types of adaptor PC boards, two mounting boxes must be mounted on the side of the main body.
Appendix Inverter K Series / PLUS Series
16
17
18
19
20
21
22
0
5
13.8
22.4
31
39.4
48.2
~
~
~
~
~
~
~
3.4
11.6
20
28.4
36.4
44.8
52.8
FXYC-K
KRP2A61
KRP1896
: http://splitoff.ru/tehn-doc.html
23
24
25
26
27
28
29
56.6
65.2
73.8
82.4
91
99.4
108.6
~
~
~
~
~
~
~
61.2
69.4
77.8
85.8
94
102.2
110.4
FXYK-K
FXYF-K
FXYS-K
FXYA-K
FXYL-K
FXYM-K
KRP2A61
KRP2A62
KRP1A90
Wiring Adaptor
30
31
32
117.2
125.8
134.2
~
~
~
119.2
127
140
FXYH-K
KRP2A62
KRP1B93
373