1.16 Drain Pump Control

1. The drain pump is controlled by the ON/OFF buttons (4 button (1) - (4) given in the figure below).
1.16.1 When the Float Switch is Tripped While the Cooling Thermostat is ON:
∗ 1. The objective of residual operation is to completely drain any moisture adhering to the fin of the indoor
unit heat exchanger when the thermostat goes off during cooling operation.
∗ 2. One cycle consists of 5 minutes of operation, 5 seconds stop, and another 5 minutes of operation.
1.16.2 When the Float Switch is Tripped During Cooling OFF by Thermostat:
Functions Inverter K Series
: http://splitoff.ru/tehn-doc.html
Functions
45