Daikin VRV Inverter K Series Manual page 105

Table of Contents

Advertisement

SI-05C.BOOK Page 91 Monday, November 6, 2000 4:13 PM
SiE-05C
Failure Diagnosis
The indoor unit display section or the separately installed receiver unit's operation lamp blinks for stop due
by Wireless Remote
to malfunction. You can diagnose the problem as described on the following page using the malfunction
Controller
code located by the method described below.
1. Push the
2. Push the time mode
3 times
1 time
Continuous beep
3. Push the operation mode selector button, and the upper digit of the malfunction code blinks.
4. Push the time mode
5. Push the operation mode selector button, and the lower digit of the malfunction code blinks.
6. Push the time mode
Note:
1. "INSPECTION" display blinks when the remote controller's
2. If you push and hold the ON/OFF button for 5 seconds or more in the INSPECTION mode, the failure
Test Operation Inverter K Series
button;
is displayed and "0" blinks.
to malfunction. A beep is then emitted to indicate signal reception.
No. of times signal reception beep is emitted
upper code.
locate the lower code.
Continuous signal reception beep indicates that the malfunction code has been ascertained.
hysteresis is canceled. In this case, after the malfunction code blinks twice, the code display changes to
"00" (normal) and the unit No. changes to "0." The mode than automatically changes from the
inspection mode to the normal mode (preset temperature display).
button and locate the number of the unit which is stopped due
Perform the procedure given below in the order of 3, 4, 5, 6.
Perform steps 3 and 6.
No malfunction
button until signal reception beeps twice, and then locate the
button until signal reception beeps continuously, and then
button is pushed.