SI-05C.BOOK Page 369 Monday, November 6, 2000 4:13 PM
SiE-05C

5. Wiring Adaptor

5.1
Wiring Adaptor for Electrical Appendices (KRP2A61·62)
Various remote control (remote control mode, remote temperature setting, display of operation, display of
malfunction) can be carried out by mounting this optional accessory in the indoor unit. Up to 64 groups of
indoor units can be monitored and controlled all at once by one adaptor PC board. The wiring adaptor for
electrical appendices cannot however be used in combination with other optional controllers for centralized
control (central remote controller, unified on/off controller, schedule timer, DDS, etc.).
5.1.1
Outline of System
1. Individual control (controls indoor units individually)
2. Group control (Simultaneously controls group-controlled indoor units [max. 16 units] all together)
3. Zone control
Appendix Inverter K Series / PLUS Series
In the case of individual display, install a wiring PC board adaptor for electrical appendices in the indoor
unit.
Simultaneously controls up to 64 groups consisting of up to 16 group-controlled indoor units each all
together (max. 64 groups × 16 units = 1,024 units).