Close in Alarm/Open in Alarm
When the Controller is set to "close in alarm," the status of the alarm
output function is output as it is. When set to "open in alarm," the sta-
tus of the alarm output function is output inverted.
Condition
Alarm
C ose
Close in
ON
alarm
l
OFF
O e
Open in
ON
alarm
l
OFF
Alarm type and close in alarm (normally open)/open in alarm (nor-
mally close) can be set independently from each alarm.
Close in alarm/Open in alarm is set in the "alarm 1 to 3 open in
alarm" parameters (setup mode). Factory setting is "close in alarm"
[ n o ].

Parameter Operations

Parameter Operation List
Switching to modes other than manual or protect mode is carried out using the mode selection in the menu display.
The figure below shows all parameters in the order that they are displayed. Some parameters are not displayed depending on the protect mode
setting and conditions of use.
Parameters and Menus
Note: For more details on the functions of each part and display contents, refer to the E5AK-T/E5EK-T/E5CK-T User's Manual
(H88/H89/H90) .
Protect Mode
Manual Mode
32
Output
Output LED
ON
Lit
OFF
Not lit
OFF
Lit
ON
Not lit
Power ON
1 second min.
Level 0 mode
1 second min.
Program mode
1 second min.
Level 1 mode
1 second min.
Level 2 mode
1 second min.
Setup mode
1 second min.
Expansion mode
1 second min.
Option mode
1 second min.
Calibration mode
The protect function is for preventing unwanted modification of parameters and switching between
run and reset operation or auto and manual operation.
In this mode, the Controller can be switched to manual operation. The manipulated variable can be
manipulated manually only in this mode.
1 second min.
Manual mode
1 second min.
1 second min.
1 second min.
Protect mode
1 second min.
E5jK-T