Omron E5xK-T series Manual page 23

Digital
Table of Contents

Advertisement

E5jK-T
CT Input/Potentiometer
When using the HBA function on the E5AK-AA2 Controller, connect CT input (CT) to terminal numbers 15 to 17. When monitoring the valve
opening on the E5AK-PRR2 Controller, connect the potentiometer (PTMR) to terminal numbers 15 to 17. Connect each of these inputs as
follows:
10
30
31 32
9
29
8
28
7
27
6
26
5
25
4
24
3
23
2
22
33
1
21
Event Input
Connect event inputs 1 and 2 (EV1/2) to terminal numbers 18 to 20, and event events 3 and 4 (EV3/4) to terminal numbers 24 to 26. However,
note that terminal numbers 18 to 20 cannot be used on Controllers with a communications function. Connect the event inputs as follows:
10
30
31 32
9
29
8
28
7
27
6
26
5
25
4
24
3
23
2
22
33
1
21
Terminals 18 and 24 (COM) are connected internally.
Use event inputs under the following conditions:
Contact input
ON: 1 kΩ max.
OFF: 100 kΩ min.
No-contact input
ON: Residual voltage 1.5 V max.,
OFF: Leakage current 0.1 mA max.
Polarities during no-contact input are as follows:
+
EV1
20
+
EV2
19
COM
18
Event input 1 and 2
20
19
18
17
16
15
14
13
12
11
20
19
18
EV1
17
16
EV2
15
COM
14
Event input 1 and 2
13
12
11
+
EV3
26
+
EV4
25
COM
24
Event input 3 and 4
17
17
16
CT
16
15
15
CT input
Potentiometer
+
20
EV3
26
+
19
EV4
25
18
COM
24
Event input 3 and 4
O
W
C
+
+
E5jK-T