External Interlock - YASKAWA GA700 Technical Manual

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

2.16 External Interlock

2.16

External Interlock

In applications where the system will be negatively impacted if the drive goes down, always create an interlock
between fault relay output (MA, MB, MC) and the DriveReady signal of multi-function digital output.
Drive Ready
When the drive is prepared for acceptance of the Run command, or is already operating, the multi-function digital
output terminal to which Drive Ready [H2-xx = 6] is set will enter the ON status.
In any of the following instances, Drive Ready is set to OFF, and Run commands will be ignored.
• when the power supply is shut off
• during a fault
• when there is problem with the control power supply
• when a parameter setting error makes the drive unable to run even if a Run command has been entered
• when a fault such as overvoltage or undervoltage is triggered as soon as the Run command is entered
• when the drive is in the Programming mode and will not accept a Run command even when entered
Interlock Circuit Example
Two drives running a single application might interlock with the controller using the Drive Ready and Fault
output signals as shown below.
Terminal
MA, MB, MC
M1-M2
84
Output Signal
Fault
Drive Ready
Figure 2.59 Interlock Circuit Example
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Parameter settings for Output signal
-
H2-01 = 06

Advertisement

Table of Contents
loading

Table of Contents