UPS MAINTENANCE
Spacers (5)
90
Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide
11. Disconnect the batteries from the wiring, and loosen the 3 nylon
straps. Retain the wiring, straps, spaces and vinyl caps. See
Figure 46 and Figure 47.
12. Remove the batteries from the tray. See "Recycling the Used
Battery or UPS" on page 94 for proper disposal of the batteries.
13. Verify that the batteries to be installed are the type listed in
"Battery Type" on page 84. Use batteries of the same age, type,
and manufacturer so that UPS performance is not affected.
14. Verify that 12 vinyl caps are installed on the battery tray dividers as
shown in Figure 46.
15. Insert eight batteries into the battery tray (see Figure 47).
16. Connect the batteries in the tray as shown in Figure 46 and
Figure 47.
17. Secure the batteries to the tray, using 5 spacers and 3 nylon straps.
See Figure 46 and Figure 47 for spacer and strap placement.
Figure 46. Battery Tray without Batteries
Vinyl Caps (12)
S
164201642 Rev C www.eaton.com/powerquality
Nylon Straps
(3)