See Figure 28 on page 55 for the location of the two X-Slot
communication bays.
Relay Interface Card
Power Xpert Gateway UPS Card
Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide
Industrial Relay Card - is used to indicate the operating status of the
UPS using the customer's monitoring equipment and to connect an
optional RMP. The IRC uses four isolated normally-open or
normally-closed dry relay contacts to indicate the UPS status. Normal,
Bypass, Battery, and Alarm mode can be monitored (see page 66 for
more information).
Power Xpert Gateway UPS Card - has SNMP and HTTP capabilities as
well as monitoring through a Web browser interface; connects to a
twisted-pair Ethernet (10/100BaseT) network. It is compatible with
Eaton IPM/IPP software, Power Xpert monitoring software, and also
provides ModBus TCP connectivity to allow setup of UPS shutdown
schedules, as well as UPS test and control. In addition, you can attach
an Environmental Monitoring Probe to obtain humidity, temperature,
smoke alarm, and security information.