Table 14. Technical Specifications
Technology
Input Voltage Range
Input Power Factor
Input Rated Voltage
Input Frequency Range
Input Rated Frequency
Output Voltage Regulation
Output Voltage Distortion
Output Frequency
Output Frequency Regulation
Output Overload
Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide
Online, double‐conversion topology with static bypass switch and
3‐position maintenance bypass switch.
Frequency independent operation.
130–249 Vac per phase
>0.99 at full load nominal line conditions
120/208 Vac three-phase
50/60-Hz selectable, auto‐configuring
±1% static, Phase to Neutral
±2% static, Phase to Phase
±5% dynamic at 100% resistive load change
Response time <1 ms
<2% THD linear load, <5% THD non‐linear load
50/60-Hz selectable or auto‐configuring
Synchronization to line
101–110% for 10 minutes
111–125% for 60 seconds
126–149% for 5 seconds
>150% for 300 milliseconds
S
164201642 Rev C www.eaton.com/powerquality
SPECIFICATIONS
45–65 Hz